Connection Hints - Siemens SIMEAS-Hub 7KE6000-8AD /CC Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

SIMEAS-Hub

Connection Hints

Auxiliary Voltage
Direct Cable Connection: Solid or stranded conductor with connector sleeve for conductor
cross-sections from 0.5 mm
of the connecting cables must be at least 300 V AC. Tightening Torque: min 0.5 Nm
The maximum rated current of the device is 0.5 A. To ensure proper selectivity in the fusing
sequence, the power supply line is to be equipped with a minimum 2 A circuit breaker (the
maximum value depends on the wiring of the cabinet). The circuit breaker must be installed
close to the device. The circuit breaker must be marked as a switch for the device.
Ethernet Connection
The rated voltage of the Ethernet connections (10Base-T) must be 300 V AC minimum.
Fibre Optic
Warning
Do not look directly into the fibre-optic elements or cables!
You have to comply with the permissible bending radii of the fibre optic cable. In other cases,
you may destroy the optical fibres.
E50417-K1074-C299-A1
2
2
to 2.5 mm
, corresponding to AWG 22 to 12. The rated voltage
English
39