Auxiliary Voltage; Current Measurement Circuits Il1-Il3, Io (Aq110P Only); Trip Relays T1, T2, T3, T4 - Siemens Arcteq AQ101 Instruction Manual

Table of Contents

Advertisement

Instruction manual AQ101, AQ101D, AQ110P, AQ01
7.1.3
A
UXILIARY VOLTAGE
Maximum interruption in normal operating state:
Maximum power consumption:
7.1.4
C
URRENT MEASUREMENT CIRCUITS
Thermal withstand continuous
Thermal withstand 1s
Thermal withstand 10s
Phase overcurrent setting range
Residual overcurrent setting range
Measurement accuracy
Rated AC Burden (VA)
7.1.5
T
RIP RELAYS
Make and carry for 0.5s
Make and carry for 3s
Breaking capacity DC, when time constant
Us (min-max):
Us (nominal)
Nominal current
Rated Frequency
Number of inputs
T1, T2, T3, T4
Number
Rated voltage
Continuous carry
L/R=40ms
Contact material
85 – 265V AC / DC
110, 220 V DC, 110, 115, 220, 230 V AC 50/60 Hz
18 – 72 V DC
24, 36, 48, 60 V DC
100 ms
5W (AQ110P)
4W (AQ101, AQ101D)
IL1-IL3, I
(AQ110P
O
1 or 5A
2...1000Hz
3 (phase) + 1 (residual)
30A
500A
100A
0.5...6 x In
0.05...2 x In
10%
Input resistance <10mΩ
3 NO + 1 NC or 4 NO
250V ac/dc
5A AC / DC
30A DC
16A DC
40W (0.36A at 110 V DC)
AgNi 90/10
)
34 (48
)
ONLY