Aq101, Aq101D Arc Flash Protection Relays - Siemens Arcteq AQ101 Instruction Manual

Table of Contents

Advertisement

Instruction manual AQ101, AQ101D, AQ110P, AQ01
Always ensure that current measurement circuits are not energized
during disconnection.
See rated voltages and connector tightening torques from chapter 7.1
"Technical data".
1.2.2
AQ101, AQ101D
Binary output 1 - +24V output
Binary output 1 – GND output
Sensor Channel 1 – Grounding
Sensor Channel 2 – Grounding
Sensor Channel 3 and 4 – Grounding
X1
S5
*) Trip contact T3 may be normally open or normally closed type. Refer to the ordering codes.
**) Sensor 5 is optional for fiber sensor. Refer to the ordering codes.
See rated voltages and connector tightening torques from chapter 7.1
"Technical data".
ARC FLASH PROTECTION RELAYS
Function
Binary input 2 – Negative
Binary input 2 – Positive
Sensor Channel 1 - Supply
Sensor Channel 1 – Signal
Sensor Channel 2 - Supply
Sensor Channel 2 – Signal
Sensor Channel 3 - Supply
Sensor Channel 3 – Signal
Sensor Channel 4 - Supply
Sensor Channel 4 – Signal
Function
Sensor 5 – Receiver **
Sensor 5 – Transmitter **
Function
Binary input 1 – Negative
Binary input 1 – Positive
Trip contact T1
Trip contact T1
Trip contact T2
Trip contact T2
Trip contact T3 *
Trip contact T3 *
Trip contact T4
Trip contact T4
Self-supervision contact – normal
Self-supervision contact – failure
Self-supervision contact – common
Power supply – positive
Power supply - negative
X2
)
10 (48
state
state

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arcteq aq101dArcteq aq110pArcteq aq01