2.1.2

AQ110P

2.1.2.1
Scheme 1a
SW 1
no
OFF
ON
8
7
6
5
4
3
2
1
SW 2
no
OFF
ON
8
7
6
5
4
3
2
1
Table 2-2: AQ110P scheme 1a DIP switches definition.
Text
8
S1: L> / L> + I>
Sensor 1 tripping with light only
7
S2: L> / L> + I>
Sensor 2 tripping with light only
6
L> / L> + I>
Tripping with light only criterion
5
a/b
4
3
Scheme
Select
2
1
Text
8
T1/T2 Latch / non
Latch.
7
HSO Latch / non
Latch.
6
S1: P> & L>
5
S5: Fib. loop /
Sensor 5 connected with fiber
Elim.
4
Fast / CBFP **
Fast mode tripping without circuit
3
100 / 150 ms *
Circuit breaker protection delay
2
I> 1A / 5A
1
Io> 1A / 5A
Function at ON position
criterion.
criterion.
Scheme a
Weight factor 0
Weight factor 0
Weight factor 0
Weight factor 0
Function at ON position
Trip relays 1 and 2 latched.
High speed outputs latched.
NA
loop sensor.
breaker failure protection.
setting 100 ms.
Phase current measurement
channels nominal rating 1 A.
Neutral current measurement
channels nominal rating 1 A.
Function at OFF position
Sensor 1 tripping with light and
current criterion.
Sensor 2 tripping with light and
current criterion.
Tripping with light and current
criterion.
Scheme b
Weight factor 8
Weight factor 4
Weight factor 2
Weight factor 1
Function at OFF position
Trip relays 1 and 2 not latched.
High speed outputs not latched.
Sensor 1 connected with AQ01
light sensor.
Sensor 5 connected with
quenching device control (TX
only).
Circuit breaker failure protection
activated.
Circuit breaker protection delay
setting 150 ms.
Phase current measurement
channels nominal rating 5 A.
Neutral current measurement
channels nominal rating 5 A.
)
13 (48