Table of Contents

Advertisement

Instruction manual AQ101, AQ101D, AQ110P, AQ01
3.1.3
S
ET BUTTON
All devices contain a set button in the front panel, which is used for installing the
system, checking the number of connected sensors and units, resetting the device
after trip event and clear the alarm signals.
Figure 3-2: Set button.
Function
Install (add binary input or
sensor amount) the system
configuration
Install (reduce binary input or
sensor amount) the system
configuration
Clear the alarm signals
Check the number of installed
sensors and unit connections
(Binary inputs) *
Reset after trip or sensor or
binary input activation
Table 3-3: Set button function vs. indication behaviors.
*) Only available at AQ101, AQ101D and AQ110P.
Instruction
Press the button for 3 seconds
Switch any DIP switch back and
forth one time, press the button
for 3 seconds
Press the button once
Press the button 3 times within 2
seconds.
Press the button once
Indications
All connected inputs LED's lit
steadily during installation.
All connected inputs LED's lit
steadily during installation.
Respective blinking led indicators
turns off
Corresponding connected input
LED blinks showing amount of
connected units and sensors.
Corresponding activated signals
and LED's turns off. Also latched
outputs resets.
)
23 (48