Trouble Shooting; Aq101, Aq101D, Aq110P Arc Flash Protection Relays - Siemens Arcteq AQ101 Instruction Manual

Table of Contents

Advertisement

Instruction manual AQ101, AQ101D, AQ110P, AQ01
6
T
ROUBLE SHOOTING
6.1
AQ101, AQ101D, AQ110P
Led:
State
Binary input
Blink
or Sensor
Others than
OFF
error
Power
OFF
Blink
All
OFF
Table 6-1: troubleshoot function description.
ARC FLASH PROTECTION RELAYS
Error led
IF relay
state
state
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
Possible issues
- Bad connection between sensors or other devices
connected to BI
- Damaged wire
- Unit amount or sensor amount changed
- Dip switch settings changed or current pick-up
potentiometer value changed > 20% (AQ110P only)
- Internal voltage too low. Auxiliary supply voltage may
be less than specified
- Input channels (binary inputs and sensor channel)
connection verification. See set button function in
chapter 3.1.3.
- Auxiliary supply voltage not connected.
)
32 (48