Technical Specifications - Siemens SIMATIC ET200SP Equipment Manual

Hide thumbs Also See for SIMATIC ET200SP:
Table of Contents

Advertisement

Technical specifications

The following table shows the technical specifications as of 05/2021. You will find a data
sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/ww/en/pv/6ES7510-1DJ01-0AB0/td?dl=en).
Article number
General information
Product type designation
HW functional status
Firmware version
Product function
I&M data
Module swapping during operation (hot
swapping)
Isochronous mode
Engineering with
STEP 7 TIA Portal configurable/integrated
from version
Configuration control
via dataset
Control elements
Mode selector switch
Supply voltage
Type of supply voltage
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Mains buffering
Mains/voltage failure stored energy time
Input current
Current consumption (rated value)
Current consumption, max.
Inrush current, max.
I²t
Power
Infeed power to the backplane bus
Power loss
Power loss, typ.
Memory
Number of slots for SIMATIC memory card
SIMATIC memory card required
28
6ES7510-1DJ01-0AB0
CPU 1510SP-1 PN
FS05
V2.9
Yes; I&M0 to I&M3
Yes; Multi-hot swapping
Yes; Only with PROFINET; with minimum OB 6x
cycle of 625 µs
V17 (FW V2.9) / V13 SP1 Update 4 (FW V1.8) or
higher
Yes
1
24 V DC
19.2 V
28.8 V
Yes
5 ms
0.6 A
0.9 A
4.7 A; Rated value
0.14 A²·s
8.75 W
5.6 W
1
Yes
CPU 1510SP-1 PN (6ES7510-1DJ01-0AB0)
Equipment Manual, 05/2021, A5E03506268-AD