System position setup

System bit is a byte of memory. It can be set through a wire controller (to input "as password).
Each bit is defined as below:
Auto: (135)
0 Power-on manual start (default)
1 Power-on auto start (in the event of power failure)
Defrost: (136)
0 "Manual defrost" in vain (default)
1 "Manual defrost" in force
Flow: (133)
0 "Water switch mode" in vain (default)
1 "Water switch mode" in force (to give an alarm in 30S upon stop of water pump if switch is in
closure)
Ambient: (139)
0 Ambient thermo probe in vain (default)
1 Ambient thermo probe in force

Operating parameter setting

The protection and operation parameters of the water chiller can be set through the controller in a
shutdown state. Default parameters are set as below:
Parameter setup
Refrigerating return water temperature
Heating return water temperature
Winter antifreezing temperature
Defrost interval
Minimum running time of defrost
a. It is recommended that refrigerating return water temperature be kept as factory setting;
b. In case actual water flow is less than 70% of rated flow, refrigerating return water
c. To prevent antifreezing alarm at low refrigerating return water temperature setting, please
PKGP-SVX03D-EN
Bit8
Bit7
Temp
Flow
otherwise low temperature setting may lead to low outlet water temperature and cause an
antifreezing alarm.
temperature setting shall be at least , otherwise the addition of antifreezing agent into
water system is necessary (volume concentration of ethylene glycol in the water system is
not lower than 15%).
increase the addition of antifreezing agent or use a large flow water pump in the water
system. Please consult Trane after-sales service personnel to modify the antifreezing setting.
Bit6
Bit5
Bit4
void
Ambient
Mode
Maximum value Minimum value
25℃
50℃
5℃
90min
8min
NOTICE:
Pre-Start-up
Bit3
Bit2
Defrost
Pulse
Regulation
precision
10℃
1℃
25℃
1℃
1℃
1℃
30min
1min
1min
1min
Bit1
Auto
Factory setting
12℃
40℃
3℃
45min
1min