3
SPECIFICATIONS
This chapter describes the specifications of the I/O module.
3.1

General Specifications

I/O module (except for waterproof module)
Item
Specifications
Operating ambient temperature
0 to 55
Storage ambient temperature
-25 to 75
Operating ambient humidity
5 to 95%RH, non-condensing
Storage ambient humidity
Vibration resistance
Compliant with JIS
B 3502 and IEC
61131-2
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z directions)
Operating atmosphere
No corrosive gases, flammable gases, less conductive dust
*1
Operating altitude
0 to 2000m
Installation location
Inside a control panel
*3
 or less
Overvoltage category
*4
Pollution degree
2 or less
Class 
Equipment class
*1 Do not use or store the I/O module (except for the waterproof module) under pressure higher than the atmospheric pressure of altitude
0m. Doing so may cause malfunction. When using the I/O module under pressure, please consult your local Mitsubishi representative.
*2 If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the module can be
used even outside the control panel.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category  applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for the
equipment with the rated voltage of 300V or less is 2500V.
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
For compliance with the EMC Directive, refer to the following:
Page 246 EMC and Low Voltage Directives
Frequency
Under intermittent
5 to 8.4Hz
vibration
8.4 to 150Hz
Under continuous
5 to 8.4Hz
vibration
8.4 to 150Hz
*2
Constant
Half amplitude
acceleration
3.5mm
9.8m/
1.75mm
4.9m/
3 SPECIFICATIONS
3.1 General Specifications
3
Number of sweeps
10 times each in X,
Y, and Z directions
19