General Information; Specifications; Operating Envelope; Use With Salt Water - Task Force Tips Typhoon Series Instructions For Installation, Safe Operation And Maintenance

Table of Contents

Advertisement

3.0 GENERAL INFORMATION

The Typhoon monitor is a 4-inch monitor. It is available in various manually operated models as well as an electric remote model.
The electric remote model is known as the Typhoon RC.

3.1 SPECIFICATIONS

Weight
Minimum Flow Area 4" Inlet
Minimum Flow Area 3" Inlet
Maximum Operating Pressure
Nominal Operating Voltage
Maximum Voltage
Minimum Voltage - 12 Volt System
Minimum Voltage - 24 Volt System
Operating Temperature Range
Maximum Torque Elevation
Maximum Torque Horizontal
Speed Elevation
Speed Horizontal
Materials Used

3.2 OPERATING ENVELOPE

WARNING
250
225
200
175
150
125
100
75
50
25

3.3 USE WITH SALT WATER

Use with salt water is permissible provided the equipment is thoroughly cleaned with fresh water after each use. The service life of
the equipment may be shortened due to the effects of corrosion, and is not covered under warranty.
©Copyright Task Force Tips LLC 2004-2020
Damage or injury could result from operating the monitor beyond the safe operating envelope.
Do not operate the monitor outside the envelope in the following graph(s).
Typhoon Operating Envelope
0
1000
2000
3000
Maximum Nozzle
Inlet Pressure
Nozzle A Inlet
Pressure
Nozzle B Inlet
Pressure
Nozzle C Inlet
Pressure
0
0
200
400
600
800
Nozzle A flows 500 gpm (1900 l/min), at 100 PSI (6.9 bar), K factor = 50
Nozzle B flows 1000 gpm (3800 l/min), at 100 PSI (6.9 bar), K factor = 100
Nozzle C flows 1500 gpm (5700 l/min), at 100 PSI (6.9 bar), K factor = 150
Nozzle D flows 2000 gpm (7600 l/min), at 100 PSI (6.9 bar), K factor = 200
Typhoon Operating Envelope
Manual
US
METRIC
26 lbs
12 kg
12.6 in
81.1 cm
2
2
7.07 in
45.6 cm
2
2
200 psi
14 bar
-30°F to +120°F (-34°C to +49°C)
ANSI A356.0-T6 Aluminum, Stainless, Nylon
Table 3.1
Flow (lpm)
4000
5000
6000
Maximum Monitor
Inlet Pressure
Nozzle D Inlet
Pressure
1000
1200
1400
1600
1800
Flow (gpm)
Figure 3.2
5
Electric
US
METRIC
38 lbs
17 kg
12.6 in
81.1 cm
2
2
7.07 in
45.6 cm
2
2
200 psi
14 bar
12 or 24 VDC (auto sense)
32 VDC
10 VDC at monitor
18 VDC at monitor
70 ft•lbs
95 n•m
60 ft•lbs
80 n•m
12 deg/sec
12 deg/sec
7000
8000
9000
16
12
8
4
0
2000
2200
2400
LIY-050 August 17, 2020 Rev14