Installation; Electrical Installation; Structural Requirements - Task Force Tips Typhoon Series Instructions For Installation, Safe Operation And Maintenance

Table of Contents

Advertisement

4.0 INSTALLATION

4.1 ELECTRICAL INSTALLATION

See Remote Control (RC) Monitor Electrical Controls Supplemental Instructions LIY-500.

4.2 STRUCTURAL REQUIREMENTS

Reaction forces generated by master stream flows are capable of causing injury and property
WARNING
damage if not properly supported. Monitors should be securely installed by qualified individuals.
The structure that the monitor is mounted to must withstand the internal pressure of the monitor as well as shear and bending forces
due to nozzle reaction. Nozzle reaction can be as high as 1100 lbs (500 kg)(2100 gpm at 100 psi).
For flanged connections, the use of flat flanges without raised faces is recommended. Use a ring gasket as defined in ASME 16.21
or ISO 7483. Tighten flange bolts in an alternating sequence as shown below. Tighten sequentially each bolt or stud three times to
30%, then 60%, and finally 100% of the specified torque. Tighten to a total of 76-80 ft-lb (100-110 N·m).
FLANGE TYPE
3" ANSI 125/150 - DN80 PN20
4" ANSI 150 - DN100 PN20
6" ANSI 150 FLANGE
DN80, PN16 FLANGE
DN100, PN16 FLANGE
©Copyright Task Force Tips LLC 2004-2020
• Mounting objects must be capable of withstanding maximum nozzle reaction force listed in
• SPECIFICATIONS.
• The monitor must be securely mounted to rigid support members.
• Do not use flanges or pipe made from plastic for monitor mounting.
• Torque all fasteners to specified values.
1
3
2
Tighten Sequentially Each Bolt Three Times to a Total of 76-80 ft-lb (100-110 N·m)
OPT#
OUTSIDE
DIAMETER
in
1
7.5
2/R
9.0
3
10.9
4
7.9
5
8.7
1
5
8
4
3
6
7
2
Figure 4.2
THICKNESS
BOLT HOLE
CIRCLE
mm
in
mm
in
190
0.75
20
6.0
230
0.94
23
7.5
277
1.0
25.4
9.5
200
0.87
22
6.3
220
0.87
22
7.1
13
4
# OF
SIZE OF BOLTS
BOLTS
mm
in
mm
152.5
4
5/8
16
190
8
5/8
16
241.3
8
3/4
19
160
8
5/8
16
180
8
5/8
16
LIY-050 August 17, 2020 Rev14