G301 = TIM (   18.00 08.30)
Example:
G302 = TIM (   08.30 18.00)
For the Zones to which this function is to be coupled the parameter "Daytime/Night = YES "(refer to Zone
programming) must be programmed. In this way the system automatically associates the high and low
sensitivity groups, so that the following two time bands are obtained:
Daytime band (low sensitivity) from 8.30 to 18. (the sensitivity values assumed by the detector are those
programmed in the "Sens-Low" item in the option folder).
Night band (high sensitivity) from 18. to 8.30. (the sensitivity values assumed by the detector are those
programmed in the "Sens-High"item in the option folder).

ZONE programming Menu

By selecting the "Zones" sub-menu you can enter a descriptive text to be associated with the selected zone.
The control unit locates by default on the first zone.
Name:
Programmable text for the ZONE
max. 32 characters
To enter the Text press the enter
to enter
key
the editing function
Through the alphanumerical
keyboard enter the zone name
at the end press the enter key
store the datum.
Day / Night : YES/NO
PAGE - 42
NOTIFIER ITALIA
to
Programming Manual
Doc. M-162.1-AM8200-ENG Rev A2
CBE of the high sensitivity group
CBE of the low sensitivity group
AM8200_manu-prog-ENG