Silence Tab; Faults Signalings Timings Tab - Honeywell NOTIFIER AM-8200 Programming Manual

Fire detection panel
Hide thumbs Also See for NOTIFIER AM-8200:
Table of Contents

Advertisement

Through the arrow keys select the item which is required to be changed ("Check " or "Check Enabl.")
through pressure of the enter key
Through the arrow keys  data are entered and through the enter key
VERIFY ENABLE: selecting "YES" the verification Function is ACTIVE with the programmed verification Time (
in seconds)

SILENCE TAB

SELF-SILENCING TIME is the time after which the output modules are reset, after being activated.
Press the right Arrow key  to change the parameters to manage the Silencing:
NOTE: the self-silencing function of each output module must be enabled in the Point Programming .
Silence Inhibit time is the time that output modules will remain active without the ability to be Silenced by an
operator.
Siren / HORN Type-ID outputs
Silence Inhibition:
Time after activation when is not possible
to Silence
Silence Autom:
Minimum activation time
Silence Autom.Enabl:
Enabling of use the Activation time
( otherways outputs are active until
Reset)
All timings are expressed in seconds,
from a minimum of 0 sec. to a max. of
255 sec.
By pressing the enter key
Through the arrows keys  data are entered and through the enter key

FAULTS signalings timings TAB

Press the right Arrow key to change the parameters to manage the Fault signallings: :
MAINS FAULT DETECTION TIME is the minimum time during which Mains Fault is signalled if there is
no mains
Mains Loss
Timings are expressed in
seconds, from a minimum of
0 sec. to a max. of 300 sec.
Through the arrow keys select the item which is required to be changed ("Mains", "Tx Faults" ) by
pressing the enter key
Through the arrow keys  data are entered and through the enter key
PAGE - 16
NOTIFIER ITALIA
the editing function is activated.
the editing function is activated.
the editing function is activated
Programming Manual
Doc. M-162.1-AM8200-ENG Rev A2
entered data are confirmed.
entered data are confirmed.
entered data are confirmed.
AM8200_manu-prog-ENG
AM_8200