CBE equation

Use the alphanumerical keyboard to enter the data
at the end, press the ENTER key on the keyboard screen to confirm.

CROSS ALARM

The parameter "Cross Alarm." is valid if the group is associated in a CBE with the "XGRP" operator.
NO = the group is active only when a thermal sensor ( a detector with HW-type-id "THER")
and an optical sensor ( a detector with HW-type-id "PHOT" ) associated with the group are in alarm.
YES = the group is active when two devices (sensors or input modules) associated with the group are in alarm.
This is the Default value.
Example of use for reverse Groups:
Have to program an OR of 16 groups
BUT
Memory is not enough !
SO
Program 2 Reverse Groups each with the CBE listing 8 Direct Groups
Then program on the Output module a CBE that sum the 2 Reverse groups
G301 = Reverse Group
G302 = Reverse Group
G301=OR(G1G2 G3 G4 G5 G6 G7 G8)
G302=OR(G9 G10 G11 G12 G13 G14 G15 G16)
L01M01=CBE=OR(G301 G302)
(
(
P
P
r
r
o
o
g
g
r
r
o
o
f
f
.
.
H
H
i
i
g
g
h
h
a
a
n
n
d
d
l
l
o
o
Can be defined as two groups (to be chosen among the inverse ones available), for which a CBE equation
must be programmed, by using the TIM operator, to make them active only during a set time.
These groups are respectively defined as: High Sensitivity Groups and Low Sensitivity Groups.
The purpose of this option is to make all installed sensors operate in control unit at high or low sensitivity when
the relevant groups are active (this will result in the DAYTIME/NIGHT function).
Note: The "Thermal Only" working mode for detectors with HW-Type _ID "OMNI" and "NFXI-SMT2" is
active automatically when the group defined as "Low sensibility" is active.
AM_8200
AM82000_manu-prog-ENG
w
w
s
s
e
e
n
n
s
s
i
i
t
t
i
i
v
v
i
i
t
t
y
y
G
G
r
r
o
o
u
u
p
p
s
s

HIGH AND LOW SENSITIVITY GROUPS