Planning; Check List - Bosch AVIOTEC IP starlight 8000 Planning Manual

Hide thumbs Also See for AVIOTEC IP starlight 8000:
Table of Contents

Advertisement

20
en | Planning
4

Planning

A fire safety analysis should be performed to determine the characteristics of the area
including a fire load calculation. The placement of the camera or cameras results from the
application environment of the customer.
4.1

Check list

It is recommended to determine the following parameters of the environment and include
them in the planning.
1.
Floor plan available?
2.
Type of monitoring:
Detectable flame and smoke sizes:
o    Standard fire (50 cm flame/75 cm smoke) o   Other requirements:
3.
Available illumination: o   Natural light
Illuminance levels:
Potential backlight:
Lighting dynamics:
Possible camera
positions:
4.
o    Given height: ______ m
[The height should be chosen so that the camera is mounted relatively flat and there are no
obstacles in the field of view of the camera.]
5.
Environmental
influences:
[Housing required]
Wiring:
Power supply:
2020.08 | 1.0 | F.01U.391.016
What is required?
What should be monitored? (Inspection may be required)
o   Area monitoring
Illumination situation
o    ______ lx
Position, window
facade
Max. lx ________
o   To be specified in
the plan
Mounting height
Miscellaneous
o   Dust
o   IP wiring
o   230 VAC with
housing
o   Yes
o   Area-of-Interest
___________________________________________
o   Artificial light
o    At least 2 lx
without IR
[Important, in order not to exceed the dynamic
factor, do not align the camera position against
windows.]
Min. lx ________
o   Specified by the
customer
o    Freely definable
o   Humidity
o   Planning the wiring
o   POE
o   24 VAC with
housing
Planning manual
AVIOTEC IP starlight 8000
o   No
o   Non-visible
illumination (IR)
o    Dynamics in the
application
[Max. factor ≤5
between max. and
min.]
o   Freely definable
o   Low temperature
(below -10°C)
o   12 VDC
o   POE + housing
Bosch Sicherheitssysteme GmbH