8.3.3.2

Configuration parameters for I/O modules

The configuration parameters are directly assigned to the respective I/O modules and are set
during device configuration. They are transferred on start-up and during re-parameterization.
PM4000 Temperature parameters
Description
Analog channel 1 measuring range
...
Analog channel 4 measuring range
Temperature channel 1 sensor type
Temperature channel 3 sensor type
Temperature channel 2 sensor type
Temperature channel 4 sensor type
Compensation procedure
When setting Pt 100/1000 (four-wire) for temperature channel 1 / 3, "none" must be selected for
1)
temperature channel 2 / 4.
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
8.3 Device/hardware configuration in the TIA Portal
Range of values
Not connected (default)
0...20 mA
4...20 mA (open-circuit detection)
None (default)
Pt 100
Pt 100 (four-wire)
Pt 1000
Pt 1000 (four-wire)
Type J thermocouple
Type K thermocouple
Type L thermocouple
None (default)
Pt 100
1)
Pt 1000
1)
Type J thermocouple
Type K thermocouple
Type L thermocouple
No compensation (default)
Internal sensor
External value
Configuration