10.3 Transfer of diagnostic alarms to the controller
10.3.3

Manufacturer-specific error codes

CIM / POM error codes
Error code
(hex)
5101
5102
5103
5104
5105
5107
5109
510C
510D
510F
5110
PM error codes
Error code
(hex)
0001
0006
0007
0008
0011
5101
510C
5112
104
Description
Communication error on HCS bus
Line voltage is outside the admissible range
(values for PM4000 U/I)
Frequency is outside the permissible range.
The error message can be initiated by any
POM.
Channel fault: Triac failed
Channel fault: Triac has high resistance / out-
going fuse blown
Channel fault: Heating element defective
Switch-off threshold for internal device temper-
ature
Channel fault: Undefined
Communication fault internal
Phase LX1 is not connected.
Phase LX3 is not connected.
Description
Short-circuit
Wire break
Measurement range / upper limit
exceeded
Measurement range / lower limit
violated
No supply voltage
Communication error on HCS bus
Undefined error
Polarity reversal at measuring input
CIM4210
-
-
-
-
-
-
-
-
PM Temperature
-
-
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
POM42xx
-
-
-
PM DI/DO
PM U/I
-
-
.
-
-
-
-
-
-
-
SIPLUS HCS4200