Features - Siemens SIPLUS HCS Operating Instructions Manual

Heating control systems
Hide thumbs Also See for SIPLUS HCS:
Table of Contents

Advertisement

System overview

3.2 Features

3.2
Features
An HCS4200 system comprises one rack with 4 or 12 slots, one Central Interface Module
(CIM) and up to 24 Power Output Modules (POM). As an option, one I/O module can be
operated on the CIM. Fan modules can be mounted on the rack. Each fan module serves 4
slots or POMs.
Image 3-1
The following types of system component are available:
System component
Rack
Central Interface Module
(CIM)
I/O module
Power Output Module
(POM)
Fan module
16
HCS4200 heating control system with rack for 12 POMs
Version
Rack 4200 for 12
POMs
Rack 4200 for 4
POMs
CIM 4210
PROFINET
CIM 4210
PROFIBUS
PM4000 DI/DO
PM4000 U/I
PM4000 Tempera-
ture
POM 4220 low-end
POM 4220 mid-range 277 V AC, 12 power outputs, max. 4432 W
FM4220
The module racks can be combined as
follows:
12 / 4 / 12+12 / 12+4 / 4+4
-
8 digital outputs and 8 configurable in-
puts/outputs
Inputs for measuring line voltage and line
current
4 analog inputs for 0...20 mA and 4 measur-
ing inputs for temperature
230 V AC, 16 power outputs, max. 1449 W
per power output
per power output
Fan module for ventilation of 4 power output
modules
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
SIPLUS HCS4200

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siplus hcs4200

Table of Contents