Section 4: Electrical Installation
March 2014
4.4.2
HART Lock
The HART Lock prevents changes to the transmitter configuration from all sources; all changes
requested via HART, LOI, and local configuration buttons will be rejected. The HART Lock can
only be set via HART communication, and is only available in HART Revision 7 mode. The HART
Lock can be enabled or disabled with a field communicator or AMS Device Manager.
Configuring HART lock using field communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Configuring HART lock using AMS Device Manager
1.
2.
3.
4.4.3
Configuration button lock
The configuration button lock disables all local button functionality. Changes to the transmitter
configuration from the LOI and local buttons will be rejected. Local external keys can be locked
via HART communication only.
Configuring configuration button lock using a field
communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Configuring configuration button lock using AMS Device Manager
1.
2.
3.
4.
5.
4.4.4
Local operator interface password
A Local Operator Interface Password can be entered and enabled to prevent review and
modification of device configuration via the LOI. This does not prevent configuration from HART
or external keys (analog zero and span; Digital Zero Trim). The LOI password is a 4 digit code that
is to be set by the user. If the password is lost or forgotten the master password is "9307".
42
Right click on the device and select Configure.
Under Manual Setup select the Security tab.
Click Lock/Unlock button under HART Lock (Software) and follow the screen prompts.
Right click on the device and select Configure.
Under Manual Setup select the Security tab.
Within the Configuration Buttons dropdown menu select Disabled to lock external local
keys.
Click Send.
Confirm service reason and click Yes.
2, 2, 6, 4
2, 2, 6, 3
Reference Manual
00809-0100-4108, Rev BA
Electrical installation