Emerson Rosemount 2090P Quick Start Manual

Pressure transmitter, with 4–20 ma hart and 1–5 vdc low power hart protocol
Hide thumbs Also See for Rosemount 2090P:

Advertisement

Quick Links

Rosemount
Pressure Transmitter
with 4–20 mA HART
HART Protocol (Revision 5 and 7)
2088, 2090F, and 2090P
®
and 1–5 Vdc Low Power
Quick Start Guide
00825-0100-4108, Rev CA
January 2018

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 2090P

  • Page 1 Quick Start Guide 00825-0100-4108, Rev CA January 2018 ™ Rosemount 2088, 2090F, and 2090P Pressure Transmitter ® with 4–20 mA HART and 1–5 Vdc Low Power HART Protocol (Revision 5 and 7)
  • Page 2: Table Of Contents

    Flameproof, or intrinsically safe (I.S.) installations. See the Rosemount 2088 Reference Manual for more information. This manual is also available electronically on Emerson.com/Rosemount. Explosions could result in death or serious injury. Installation of these transmitters in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
  • Page 3: System Readiness

    The Rosemount 2088, 2090F, and 2090P Transmitters all use Rosemount 2088 Device Revisions and Drivers. 1. Download the latest DD at Emerson.com or FieldCommGroup.org. 2. In the Browse by Member dropdown menu, select Emerson. 3. Select desired product. a. Reference Table 1 Table 2, Find Device Driver Files column to find the correct device driver.
  • Page 4: Mount The Transmitter

    2-in. pipe using an optional mounting bracket. Rosemount 2090P Mount directly to the process pipe using an existing weld spud, or have a skilled welder install a new weld spud using a TIG welder. See Rosemount 2088 Reference Manual for complete welding instructions.
  • Page 5 Figure 1. Transmitter Direct Mounting Do not apply torque directly to the electronics housing. To avoid damage, apply torque only to the hex-shaped process connection. Rosemount 2088 Rosemount 2090P Rosemount 2090F 1.5 in. 1.0 in. –14 NPT female process connection D.
  • Page 6 January 2018 Quick Start Guide Gas flow applications 1. Place taps in the top or side of the line. 2. Mount level or above the taps. Steam flow applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3.
  • Page 7: Set The Switches

    Quick Start Guide January 2018 Set the switches Set alarm and security switch configuration before installation as shown in Figure The alarm switch sets the analog output alarm to high or low. Default alarm  is high. The security switch allows ( ) or prevents ( ) any configuration of the ...
  • Page 8: Connect The Wiring And Power Up

    January 2018 Quick Start Guide Connect the wiring and power up Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5000 ft. (1500 m) in length. If applicable, install wiring with a drip loop.
  • Page 9: January

    Quick Start Guide January 2018 Use the following steps to wire the transmitter: 1. Remove the housing cover on the FIELD TERMINALS side. 2. Connect the leads as shown in Figure 5 Figure 3. Tighten the terminal screws to ensure full contact with the terminal block screw and washer.
  • Page 10: Verify Transmitter Configuration

    Refer to Table 4 and the appropriate column based on your Field Revision and HART Revision for Fast Key sequences. Note Emerson recommends installing the latest DD to access the complete functionality. Visit Emerson.com or FieldCommGroup.org. Figure 8. Traditional Interface...
  • Page 11 Quick Start Guide January 2018 Figure 9. Device Dashboard Note A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure. Table 3. Traditional Interface Fast Key Function Fast Key sequence ...
  • Page 12 January 2018 Quick Start Guide Table 3. Traditional Interface Fast Key Function Fast Key sequence Scaled D/A Trim (4–20 mA) 1, 2, 3, 2, 2 Self Test (Transmitter) 1, 2, 1, 1 Sensor Info 1, 4, 4, 2 Sensor Trim (Full Trim) 1, 2, 3, 3 Sensor Trim Points 1, 2, 3, 3, 5...
  • Page 13 Quick Start Guide January 2018 Table 4. Device Dashboard Fast Keys Function Fast Key Sequence Field Revision Rev 3 Rev 5 Rev 7 HART Revision HART 5 HART 5 HART 7 Scaled Variable 3, 2, 2 3, 2, 2 HART Revision 5 to HART Revision 7 switch 2, 2, 5, 2, 3 2, 2, 5, 2, 3 Long Tag...
  • Page 14: Trim The Transmitter

    January 2018 Quick Start Guide Figure 11. LOI Menu Assign PV HART Revision Switch HART revision mode If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 2088, 2090F, or 2090P will load a generic menu with limited capability.
  • Page 15 Quick Start Guide January 2018 b. Digital zero trim – recalibrates the sensor zero. The LRV is unaffected. The pressure value will be zero (on display and  HART output). 4 mA point may not be at zero. This requires that the factory calibrated zero pressure is within a range ...
  • Page 16: Safety Instrumented Systems Installation

    January 2018 Quick Start Guide Perform trim with analog zero and span (option D4 or standard on Rosemount 2090F and 2090P) 1. Set the transmitter pressure. 2. Press and hold the Zero button for two seconds to perform an analog zero trim.
  • Page 17: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Ordinary Location Certification As standard, the transmitter has been examined and tested to determine that...
  • Page 18 January 2018 Quick Start Guide Special Conditions for Safe Use (X): 1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
  • Page 19 Quick Start Guide January 2018 International K7 IECEx Flameproof Certificate: IECEx KEM 06.0021X Standards: IEC60079-0:2011, IEC60079-1:2014, IEC60079-26:2014 ≤ T ≤ ≤ T ≤ Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C +70 °C), T4/T5(–60 °C +80 °C) Special Condition for Safe Use (X): 1.
  • Page 20 January 2018 Quick Start Guide NK IECEx Dust Certificate: IECEx BAS12.0073X Standards: IEC60079-0:2011, IEC60079-31:2008 Markings: Ex t IIIC T50 °C T 60 °C Da Table 9. Input Parameters Parameter HART Voltage U 36 Vdc Special Conditions for Safe Use (X): 1.
  • Page 21 Quick Start Guide January 2018 GB3836.4-2010. Technical Regulations Customs Union (EAC) EM EAC Flameproof Certificate: RU C-US.GB05.B.01197 ≤ T ≤ ≤ T ≤ Markings: Ga/Gb Ex d IIC T4/T6 X, T4(–40 °C +80 °C), T6(–40 °C +40 °C) Special Condition for Safe Use (X): 1.
  • Page 22 January 2018 Quick Start Guide Table 11. Thread Adapter Thread Sizes –14 NPT –14 NPT PG 13.5 PG 13.5 Special Condition for Safe Use (X): 1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e”...
  • Page 23 A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Ordinary Location Certification As standard, the transmitter has been examined and tested to determine that...
  • Page 24 January 2018 Quick Start Guide Special Conditions for Safe Use (X): 1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
  • Page 25 Quick Start Guide January 2018 International E7 IECEx Flameproof Certificate: IECEx KEM 06.0021X Standards: IEC 60079-0:2011, IEC60079-1:2014, IEC60079-26:2014 ≤ T ≤ ≤ T ≤ Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C +70 °C), T4/T5(–60 °C +80 °C) Special Conditions for Safe Use (X): 1.
  • Page 26 January 2018 Quick Start Guide Table 14. Input Parameters Parameter HART Voltage U 36 V Special Conditions for Safe Use (X): 1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
  • Page 27 Quick Start Guide January 2018 2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0. China E3 China Flameproof Certificate: GYJ15.1505 Standards: GB3836.1-2010, GB3836.2-2010 ≤...
  • Page 28 January 2018 Quick Start Guide Korea EP Korea Flameproof Certificate: 13-KB4BO-0020X ≤ T ≤ ≤ T ≤ Markings: Ex d IIC T6…T4, T4/T5(–60 °C +80 °C), T6(–60 °C +70 °C) Special Condition for Safe Use (X): 1. See certificate for special conditions. Japan E4 Japan Flameproof Certificate: TC20869, TC20870...
  • Page 29 Quick Start Guide January 2018 Table 16. Conduit Plug Thread Sizes Thread Identification mark M20 x 1.5–6g –14 NPT Table 17. Thread Adapter Thread Sizes Male thread Identification mark M20 x 1.5–6H –14 NPT –14 NPT –14 NPT –14 NPT Female thread Identification mark M20 x 1.5–6H...
  • Page 30 January 2018 Quick Start Guide Enclosure Lloyds Register (LR) Type Approval Certificate: 11/60002 Application: Environmental categories ENV1, ENV2, ENV3, and ENV5...
  • Page 31: Eu Declaration Of Conformity

    Quick Start Guide January 2018 Figure 13. Rosemount 2088 and 2090 Declaration of Conformity EU Declaration of Conformity No: RMD 1010 Rev. L Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 declare under our sole responsibility that the product, Rosemount Pressure Transmitters 3051P, 2051G, 2088, and 2090 manufactured by, Rosemount, Inc.
  • Page 32 January 2018 Quick Start Guide EU Declaration of Conformity No: RMD 1010 Rev. L EMC Directive (2014/30/EU) Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013 ATEX Directive (2014/34/EU) BAS00ATEX1166X - Intrinsic Safety Certificate Equipment Group II Category 1 G Ex ia IIC T4 Ga Harmonized Standards: EN60079-0:2012 + A11:2013, EN60079-11:2012 BAS00ATEX3167X - Type n Certificate...
  • Page 33 Quick Start Guide January 2018 EU Declaration of Conformity No: RMD 1010 Rev. L ATEX Notified Bodies DEKRA (KEMA) [Notified Body Number: 0344] Utrechtseweg 310, 6812 AR Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands Postbank 6794687 SGS Baseefa Limited [Notified Body Number: 1180] Rockhead Business Park Staden Lane Buxton, Derbyshire...
  • Page 34 January 2018 Quick Start Guide Rosemount 2088, 2090F, and 2090 China RoHS List of Rosemount 2088, 2090F, and 2090 Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd)
  • Page 35 Quick Start Guide January 2018...
  • Page 36 +65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com Emerson Terms and Conditions of Sale are available upon request The Emerson logo is a trademark and service mark of Emerson Middle East and Africa Regional Office Electric Co. Emerson Automation Solutions Rosemount and Rosemount logotype are trademarks of Emerson.