5. Operating Instructions

5.1 Exporting the Initial Settings of the EB-50

How to export the Initial Settings from the EB-50 to be used with the InterlockConfigTool will be explained
below.
Important
・Before using the InterlockConfigTool, make sure the Interlock Control license for the EB-50 is
valid.
The InterlockConfigTool cannot be used without a valid Interlock Control license.
* Refer to the EB-50 Operation Manual for how to check the validity status of the Interlock
Control license.
・After data is exported to an HDD or a USB memory, edited with InterlockConfigTool, and
imported back into the EB-50, do not make any settings changes (e.g., group settings) on
the EB-50. If any changes are made before the exported data is imported back, the EB-50
will not function properly.
[Operating Procedures]
Note
・If the Interlock Control is already in use on the EB-50, skip steps (1) and (2) below.
(1) Click "Function 3" then "Interlock control" from
the menu on the EB-50's Initial Setting Web
browser to open the Interlock control settings
screen.
(2) Click "Execute" at the left top area then "Save
settings" at the right bottom area.
(3) Click "Utility" then "Back up/import setting data"
from the menu on the EB-50's Initial Setting
Web browser to open the Back up/import
settings screen.
11