Check code
Location
Outdoor 7-segment display
Main
remote
detection
Check
Sub-code
controller
code
IPDU
F13
F13
I/F
F15
F15
I/F
F16
F16
I/F
F23
F23
I/F
F24
F24
Indoor
F29
unit
I/F
F31
F31
IPDU
H01
H01
IPDU
H02
H02
of
Description
System status
TH sensor error
All stop
Outdoor
All stop
temperature
sensor wiring
error (TE, TL)
Outdoor
All stop
pressure sensor
wiring error (Pd,
Ps)
Ps sensor error
All stop
Pd sensor error
All stop
Other indoor
Stop of
error
corresponding
unit
Outdoor
All stop
EEPROM error
Compressor
All stop
breakdown
Compressor
All stop
error (lockup)
98
121
Error detection
Check items (locations)
condition(s)
Sensor resistance is zero
Defect in IGBT built-in
(short circuit).
temperature sensor
Replace IPDU P.C.
board.
During compressor operation
Check installation of TE
in HEAT mode, TE
and TL sensors.
continuously provides
Check resistance
temperature reading higher
characteristics of TE and
than indicated by TL by at
TL sensors.
least specified margin for 3
Check for outdoor P.C.
minutes or more.
board (I/F) error.
Readings of high-pressure
Check connection of high-
Pd sensor and low-pressure
pressure Pd sensor
Ps sensor are switched.
connector.
Output voltages of both
Check connection of low-
sensors are zero.
pressure Ps sensor
connector.
Check for defect in
pressure sensors Pd and
Ps.
Check for error in outdoor
P.C. board (I/F).
Check for deficiency in
compressive output of
compressor.
Check 4-way valve error.
Output voltage of Ps sensor
Check for connection error
is zero.
involving Ps sensor and Pd
sensor connectors.
Check connection of Ps
sensor connector.
Check for defect in Ps
sensor.
Check for deficiency in
compressive output of
compressor.
Check for defect in 4-way
valve.
Check for defect in outdoor
P.C. board (I/F).
Check for defect in SV4
circuit.
Output voltage of Pd sensor
Check connection of Pd
is zero (sensor open-
sensor connector.
circuited).
Check for defect in Pd
Pd > 4.15 MPa despite
sensor.
compressor having been
Check for defect in outdoor
turned off.
P.C. board (I/F).
Indoor P.C. board does not
Check for defect in indoor
operate normally.
P.C. board (faulty
EEPROM)
Outdoor P.C. board (I/F)
Check power supply
does not operate normally.
voltage.
Check power supply noise.
Check for defect in outdoor
P.C. board (I/F).
Inverter current detection
Check power supply voltage.
circuit detects overcurrent
(AC220-240V ± 10%).
and shuts system down.
Check for defect in
compressor.
Check for possible cause
of abnormal overloading.
Check for defect in outdoor
P.C. board (IPDU).
Overcurrent is detected
Check for defect in
several seconds after startup
compressor.
of inverter compressor.
Check power supply voltage.
(AC220-240V ± 10%).
Check compressor system
wiring, particularly for open
phase.
Check connection of
connectors / terminals on
IPDU P.C. board.
Check for defect in outdoor
P.C. board (IPDU).