Table of Contents

Advertisement

Quick Links

SERVICE MANUAL
AIR-CONDITIONER (MULTI TYPE)
OUTDOOR UNIT
Model name:
MCY-MHP0806HS8-E
MCY-MHP1006HS8-E
MCY-MHP0806HS8-TR
MCY-MHP1006HS8-TR
This service manual provides relevant explanations about new outdoor unit.
Please refer to the following service manuals for each indoor units.
<4-way Cassette Type>
(MMU-AP****HY)
<Compact 4-way Cassette Type>
(MMU-AP****MH*)
<2-way Cassette Type>
(MMU-AP****WH*)
<1-way Cassette Type>
(MMU-AP****YH*)
(MMU-AP****SH*)
<Concealed Duct Standard>
(MMD-AP****BH*)
(MMD-AP****BHY*)
<Concealed Duct High Static Pressure Type>
(MMD-AP****H*)
(MMD-AP0726,P0966HP*)
<Slim Duct Type>
(MMD-AP****S(P)H*)
(MMD-AP024, A0274SPH*)
<Compact Slim Duct Type>
(MMD-AP***M(P)H*)
(MMD-AP***M(P)HY*)
<Ceiling Type>
(MMC-AP****H*)
(MMC-AP****HP*)
<Floor Standing Cabinet Type>
(MML-AP****H*)
<Floor Standing Concealed Type>
(MML-AP****BH*)
<Floor Standing Type>
(MMF-AP****H*)
<High Wall Type>
(MMK-AP****H*)
(MMK-AP****HP*)
<Console Type>
(MML-AP****NH*)
<HWM Type>
(MMW-AP****LQ*)
MCY-MHP0806HT8-C*
MCY-MHP0906HT8-C*
MCY-MHP1006HT8-C*
Service Manual No.
(Made in China model)
(Made in China model)
(Made in Thailand model)
(Made in China model)
(Made in Thailand model)
(Made in Thailand model)
(Made in Thailand model)
(Made in Thailand model)
A10-1402
A10-033
A10-007
A10-033
A10-033
A10-033
A10-1415
A10-033
SVM-16038
A10-033
A12-005
A10-1612
A10-1403
A10-033
SVM-17015
A10-033
A10-033
A10-033
SVM-17053
SVM-17085
SVM-11036
A10-1505
FILE NO. A10-1908

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba MCY-MHP0806HT8-C Series

  • Page 1 FILE NO. A10-1908 SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) OUTDOOR UNIT Model name: MCY-MHP0806HS8-E MCY-MHP0806HT8-C* MCY-MHP1006HS8-E MCY-MHP0906HT8-C* MCY-MHP0806HS8-TR MCY-MHP1006HT8-C* MCY-MHP1006HS8-TR This service manual provides relevant explanations about new outdoor unit. Please refer to the following service manuals for each indoor units. Service Manual No.
  • Page 2: Table Of Contents

    Contents Precautions for safety ..........7 1 Product summary .
  • Page 3 8 Test operation ............
  • Page 4 10 Outdoor unit parts replacement methods ....... . 153 11 P.C. board exchange procedures........173 11-1.
  • Page 5 • The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation...
  • Page 6 Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
  • Page 7 Warning indications on the air conditioner unit [Confirmation of warning label on the main unit] Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original. WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing.
  • Page 8: Precautions For Safety

    Precautions for safety The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. DANGER Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker for both the indoor and outdoor units to the OFF position.
  • Page 9 WARNING Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions. Only qualified service person is allowed to repair the air conditioner. Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury, water leaks and/or other problems.
  • Page 10 If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical control box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, put a sign in place so that no-one will approach the Do not bring a work location before proceeding with the work.
  • Page 11 When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cooking stove though the refrigerant gas itself is innocuous.
  • Page 12 Only a qualified installer or qualified service person is allowed to install the air conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result. Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.
  • Page 13 Declaration of Conformity Manufacturer: Toshiba Carrier Air Conditioning (China) Co., Ltd. Building 1, No.60, 21st Avenue and 2nd Floor, Building 3, No.235, 23st Avenue, Baiyang Street, Hangzhou Economic and Technological Development Area, China. TCF holder: TOSHIBA CARRIER EUROPE S.A.S Route de Thil...
  • Page 14 New refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety caution concerned to new refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed.
  • Page 15 4. Tools (1) Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) 2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) 3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
  • Page 16: Product Summary

    Product summary 1-1. Outdoor unit For Europe and Turkey model Corresponding HP Power supply 10HP Power supply MCY-MHP0806HS8-E MCY-MHP1006HS8-E Three-phase MCY-MHP0806HS8-TR MCY-MHP1006HS8-TR 380-415V (50Hz) Cooling capacity (kW) * 22.4 28.0 Heating capacity (kW) * 22.4 28.0 For China model Corresponding HP Power supply 10HP Power supply...
  • Page 17: Branching Joints And Headers

    1-3. Branching joints and headers Model name Appearance RBM-BY55E i o j RBM-BY105E 1-4. PMV kit Model type Indoor unit capacity type Appearance RBM-PMV0363E, RBM-PMV0361U-E 005 to 014 type RBM-PMV0903E, RBM-PMV0901U-E 015 to 027 type...
  • Page 18: Construction Views

    Construction views...
  • Page 20: Wiring Diagram

    Wiring diagram...
  • Page 21: Parts Rating

    Parts rating 4-1. Outdoor unit RA641A3TB-22M Output: 5.60 kW 4-way valve coil SQ-A2522G-000371 AC220-240V, 50/60Hz FQ-G593 AC220-240V, 50/60Hz SV2, SV4, SV5 valve coil TEV-SMOAJ2170A1 AC220-240V, 50Hz SV3 valve coil Pulse motor valve coil PAM-MD12TF-1 DC12V Pulse motor valve coil 4 PQ-M10012-000441 DC12V YCQB04H02...
  • Page 22: Parts Layout In Outdoor Unit

    4-3. Parts layout in outdoor unit SV2 valve SV5 valve SV4 valve 4-way valve TS3 sensor Low pressure sensor TS1 sensor High pressure sensor High pressure sw PMV4 (Pulse Motor Valve) TL1 sensor PMV1 (Pulse Motor Valve) Check joint (Low pressure) Check joint (High pressure) TL3 sensor...
  • Page 23: Parts Layout In Inverter Assembly

    4-4. Parts layout in inverter assembly Magnetic contactorinverter Inverter P.C. board for compressor [A3 IPDU] PTC themistor (MCC-1729) Noise filter P.C.board Inverter P.C. board for lower fan (MCC-1733) [Fan IPDU] (MCC-1728) Power supply terminal block Communication terminal block Interface P.C. board [Outdoor control P.C.
  • Page 24: Outdoor (Inverter) Print Circuit Board

    4-5. Outdoor (inverter) print circuit board 4-5-1. Interface P.C. board (MCC-1639) SW 04,05,06 Option input/output 7-segment LED Jumper select CN508 CN510 CN513 SW 01,02,03 CN511 CN509 CN512 TD CN502 TS3 CN506 TS1 CN505 TK CN918 TO CN507 TE CN520 TL3 CN525 TL1 CN523 SW06,07,09,10 SW11,12,13,14 SW 16,17...
  • Page 25: Inverter P.c. Board For Compressor (Mcc-1729) A3-Ipdu

    4-5-2. Inverter P.C. board for compressor (MCC-1729) A3-IPDU Power supply output (reactor) Power supply Input (L3) CN04 CN03(Black) Power supply Input (L2) CN02(White) Power supply Input (L1) CN01(Red) Compressor output Power supply output (rector) U-phase CN05 CN201(Red) Compressor output U-phase CN202(White) UART communication Compressor output...
  • Page 26: Fan Motor Ipdu (Mcc-1728) For Upper Fan And Center Fan

    4-5-3. Fan motor IPDU (MCC-1728) Fan motor output (Lower fan) Fan motor CN750 (White) output (Upper fan) CN700 (Blue) DC280V output CN502 (White) Power supply input and reactor Connecting CN500 (Red) UART UART communication communication CN504 (Blue) CN505 (Red)
  • Page 27: Noise Filter (Mcc-1733)

    4-5-4. Noise filter (MCC-1733) Power supply Power supply Input (L1) output (L1) CN01 (Red) CN21 (Red) Power supply Power supply Input (L2) output (L2) CN22 (White) CN02 (White) Power supply Power supply Input (L3) output (L3) CN03 (Black) CN23 (Black) Power supply output Power supply...
  • Page 28: Refrigerant Piping Systematic Drawing

    Refrigerant piping systematic drawing Outdoor unit Sensor(TO) Heat exchanger (PMV1) Sensor(TE) Strainer 弁Capillary tube Solenoid Valve (SV5) Sensor(TL1) 4-Way valve Check joint Sensor(TS1) Check Valve Check joint Sensor (TS3) Solenoid Valve High pressure Low Pressure (SV4) SensorAG- sensorW L25YLTF-1 High Pressure 弁Capillary tube Muffler...
  • Page 29 Explanation of functional parts Functional part na (Hot gas bypass) (Connector CN311 : White) 1) Low pressure release function 2) High pressure release function 3) Gas balance function during stop time 4) Hot gas bypass into accumulator (Connector CN316: Black) 1) For returning oil to compressor (Start compensation valve of compressor) Solenoid valve...
  • Page 30: Control Outline

    Control outline Outdoor unit Item Description of operation, numerical data, and other information Remarks 1. Pulse 1) PMV1 control motor valve • During air conditioner operation, the pulse count of the PMV1 (pulse motor valve1) (PMV) is controlled between 100 and 3000. control •...
  • Page 31 Item Description of operation, numerical data, and other information Remarks 2. Outdoor 2. Heating fan control fan control 1) Outdoor fan speed (mode) is controlled on the basis of measurements provided by (continued) the TE temperature sensor. 2) If TE > 25 °C is continuously detected for 5 minutes, the operation may stop. 3) For a specified period after air conditioner startup and during defrosting, this control is disabled.
  • Page 32 Item Description of operation, numerical data, and other information Remarks 2. Heating refrigerant (oil) recovery control Refrigerant / During heating operation, this control function is executed to recover liquid refrigerant Oil recovery from indoor units.It is also executed to recover indoor/outdoor refrigerant after defrosting control and to recover oil in outdoor heat exchangers during heating overload operation.
  • Page 33 Item Description of operation, numerical data, and other information Remarks 1. SV2 gas balance control 8. Release This control function is aimed at achieving gas balance by opening SV2 while valve control compressor is turned off so as to reduce its startup load the next time it is turned on.
  • Page 34 Item Description of operation, numerical data, and other information Remarks 9. Frequency High pressure release control release This function is to correct the operation command of the compressor and suppress the control rise of high pressure. 1. Cooling frequency release control 1) Control contents The operation frequency is decreased by 1 step when PD pressure ≥3.8 MPa.
  • Page 35 Item Description of operation, numerical data, and other information Remarks 10. A3-IPDU 2. Heat sink temperature detection control • A3-IPDU is provided with a TH sensor. control 1) This control performs the IGBT overheat protection by the detection of the TH (continued) sensor in Module Q201 for compressor driven in A3-IPDU.
  • Page 36 <Other points to note> Cooling operation under low outside temperature conditions 1) If pressure falls to extremely low levels, indoor units may be shut down via freeze prevention control based on the indoor TC sensor. 2) If pressure falls to extremely low levels, frequency may be reduced via cooling capacity control. 3) When the discharge temperature sensor reading falls below 60 °C, the frequency may be increased above the level called for by the command received from the indoor unit.
  • Page 37: Applied Control For Outdoor Unit

    Applied control for outdoor unit The outdoor fan high static pressure support and priority operation mode setting (cooling / heating / number of units / or priority indoor unit) functions are made available by setting relevant switches provided on the interface P.C.
  • Page 38 (2) Indoor unit setup method for priority indoor unit mode The setting can be changed only when the system is at rest. (Be sure to turn off the system prior to this operation.) Push the buttons simultaneously and hold for at least 4 seconds.
  • Page 39: Applied Control Of Outdoor Unit

    7-3. Applied control of outdoor unit 7-3-1. Optional P.C. board of outdoor unit installation Placing position Install the optional P.C. boards on top of the interface P.C. board in the outdoor unit. Be sure to turn off the power switch before installing. (1) Holes for installing supports are provided on the top of the interface P.C.
  • Page 40 Optional control P.C. boards provide access to a range of functions as listed below. Control P.C. board to be used Outdoor unit interface P.C. board setting* Jumper to be PCDM4E PCMO4E PCIN4E Connector No. DIP SW No. removed Power peak-cut control (Standard) –...
  • Page 41: Power Peak-Cut Control (Standard)

    7-3-2. Power peak-cut control (standard) L1: Display lamp ensuring power peak cut control Outdoor unit Locally procured Optional PCB Power Display Outdoor unit supply relay interface PCB [OPERATION] Shield wire PJ17 CN513 SW07 [ON] [OFF] Bit 2 OFF Shield Connection cable wire For SW1 and SW2, be sure to provide no- voltage contacts for each terminal.
  • Page 42: Power Peak-Cut Control (Extended)

    <SW07 Bit 2 OFF (two-step control)> Power peak-cut control is enabled as long as SW1, as shown on the wiring diagram, is ON (continuously). Jumper wire Input 0 % (forced stop) 60 % capacity (upper limit regulated) 100 % (normal operation) 100 % (normal operation) Note 1: Specifications of display relay contact •...
  • Page 43: Snowfall Fan Control

    7-3-4. Snowfall fan control Outdoor unit Locally procured Connection Outdoor unit Optional PCB Snowfall sensor cable interface PCB COOL Shield HEAT wire SW1: Snowfall detection switch (snowfall sensor) Operation An external snowfall signal turns on the outdoor unit fan. Terminal Input signal Operation Snowfall fan control...
  • Page 44: Night Operation (Sound Reduction) Control

    7-3-6. Night operation (sound reduction) control Outdoor unit Locally procured Connection Outdoor unit Optional PCB cable interface PCB COOL HEAT Shield wire SW1: Night time signal switch Operation This function decreases noise at night or other times as necessary. Terminal Input signal Operation Night time control...
  • Page 45: Operation Mode Selection Control

    7-3-7. Operation mode selection control Outdoor unit Locally procured Connection Outdoor unit Optional PCB cable interface PCB COOL HEAT Shield wire SW1: Cooling mode specified input switch SW2: Heating mode specified input switch NOTE SW1: COOL mode selection switch SW2: HEAT mode selection switch Input signal Operation Remarks...
  • Page 46: Error / Operation Output

    7-3-8. Error / Operation output Locally procured Outdoor unit (See “NOTE”) Outdoor unit Optional PCB interface PCB OUTPUT1 SW16 OUTPUT2 OUTPUT3 Shield wire Operation In-operation output: An in-operation indication signal is output as long as at least one indoor unit is in operation in the line.
  • Page 47: Test Operation

    Test operation 8-1. Procedure and summary of test operation A test operation is executed with the following procedure.When a problem occurs at any step, remove the causes of the problem referring to “9 Troubleshooting.” This main power supply check shall be done before operation Checks before test operation switch turns ON This main power supply check shall be done before operation...
  • Page 48: Check Items Before Test Operation (Before Powering-On)

    8-2. Check items before test operation (before powering-on) Prior to the test operation, check the following items to verify there are no problems with the installation work. Main check items for electric wiring The communication system differs from that of R22 or R407 refrigerant “Modular Multi system” air conditioners. Check wiring points again carefully.
  • Page 49 (2) In the case that a central control system is connected (before address setup) Central remote controller (1) (2) To other refrigerant line Other refrigerant line SW13 SW14 CN10 SW13 SW14 Outdoor unit CN10 CN02 SW30 CN02 SW30 To indoor unit Indoor unit Remote Remote...
  • Page 50 Checklist 1 Using Checklist 1, check that there are no problems with the installation work. Is the capacity of the circuit breaker Outdoor unit Indoor unit (Earth leakage breaker) appropriate? Is the gauge of the Outdoor unit Indoor unit power cable correct? n i l Central control system connection terminals (U3, U4) Is the power of indoor units supplied collectively?
  • Page 51 For Europe and Turkey model Checklist 2 Calculate the additional amount of refrigerant from the following: Additional refrigerant Corrective amount of Additional refrigerant Compensation by Real length of liquid charge amount per 1 m refrigerant depending charge amount at local outdoor HP pipe liquid pipe...
  • Page 52 For China model Checklist 2 Calculate the additional amount of refrigerant from the following: Additional refrigerant Corrective amount of Additional refrigerant Compensation by Real length of liquid charge amount per 1 m refrigerant depending charge amount at local outdoor HP pipe liquid pipe on the indoor units...
  • Page 53: Check At Main Power-On

    8-3. Check at main power-on After turning on the main power of the indoor units and outdoor unit in the refrigerant line to conduct a test operation, check the following items in each outdoor and indoor unit. (After turning on the main power, be sure to check in order: indoor unit outdoor unit.) <Check on the outdoor unit>...
  • Page 54: Address Setup

    8-4. Address setup This product requires address setup before operation. Follow this procedure for address setup. 8-4-1. Precautions (1) Address setup is not performed simply by turning on the power supply. (2) For indoor units, address setup can be done either by manual address setup or by automatic address setup: Automatic address setup: Setup from SW15 on the interface P.C.
  • Page 55: Address Setup Procedure

    8-4-3. Address setup procedure (Single refrigerant line): ress setting procedure 1 Central control of 2 or more refrigerant lines: go to Address setting procedure 2 When controlling a single refrigerant line When controlling 2 or more refrigerant lines (Example) centrally centrally Address setting procedure...
  • Page 56 (Example) Controlling 2 or more refrigerant lines as a group Outdoor Outdoor System wiring diagram Indoor Indoor Indoor Indoor (Group control) Remote controller Address setting procedure 2 Set a line address for each system using SW 13 and 14 on the interface P.C. board on the outdoor unit of each system.
  • Page 57 Be sure to disconnect the relay connectors CN10 which mounted interface P.C. board from CN02, on all the outdoor unit that will be connected to the central control. CN02 CN10 Communication terminal board Turn on indoor units first, and then turn on outdoor unit. About 1 minute after turning the power on, confirm that the 7-segment display on the interface U.
  • Page 58 Set the central control address. (For the setting of the central control address, refer to the installation manuals of the central control devices.) Outdoor unit interface P.C. board 7-segment display SW30 * Outdoor units are connected to the same central control, except the outdoor unit with the smallest line address number.
  • Page 59 Switch setting (setting example when controlling 2 or more refrigerant lines centrally) Outdoor units (setting manually) *The items in bold font must be set manually. Outdoor unit’s Outdoor unit Outdoor unit Outdoor unit Factory default interface P.C. board SW13, 14 (Line (system) address) DIP switch 2 of SW30 Set to OFF...
  • Page 60 Manual address setting with the remote controller Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started (manual setting using the remote controller) Wiring example of 2 refrigerant lines Refrigerant line 1 Refrigerant line 2 Outdoor...
  • Page 61 <Line (system) address> Push the TEMP. buttons repeatedly to set the CODE No. to Push the TIME buttons repeatedly to set a line address. (Match the address with the address on the interface P.C. board of the outdoor unit in the same refrigerant line.) Push button.
  • Page 62 Confirming the indoor unit addresses and the position of an indoor unit using the remote controller Confirming the numbers and positions of indoor units To see the indoor unit address of an indoor unit having location data. When the unit is individual (the indoor unit is paired with a wired remote controller one-to-one), or it is a group-controlled one.
  • Page 63 (Execute it while the units are stopped.) The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are activated. Push and hold the buttons at the same time for more than 4 seconds. •...
  • Page 64 To select another line address Push the button to return to step • After returning to step , select another line address and check the indoor unit addresses of the line. Push the button to finish the procedure. Changing the indoor unit address using a remote controller To change an indoor unit address using a wired remote controller.
  • Page 65 To change all the indoor unit addresses using an arbitrary wired remote controller. (The method is available when the addresses have already been set automatically.) (When communication wirings of 2 or more refrigerant lines are interconnected for central control) NOTE You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
  • Page 66 Push the TIME buttons repeatedly to change the value of the indoor unit address in SET DATA. Change the value in SET DATA to that of a new address. Push the button to confirm the new address on SET DATA. Push the button (left side of the button) repeatedly to select another address to change.
  • Page 67 Turn on the indoor and outdoor units of the refrigerant line to be initialized in addresses. About one minute after turning on the power, confirm that the 7-segment display on the outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the outdoor unit of the refrigerant line as follows.
  • Page 68 In the case of an increase in address-undefined indoor units (extension, etc.) To set up the indoor address of a unit with an address that is undefined due to the extension of indoor units or replacement of P.C. board, etc., follow the methods below. Method 1 Set up an address individually from a wired remote controller.
  • Page 69: Check After Address Setup When Central Control System Is Connected

    8-4-4. Check after address setup when central control system is connected When the central control system is connected, check that the following setup has finished after address setup. Central remote controller To other refrigerant line Other refrigerant line Outdoor unit Outdoor unit Outdoor unit SW13 SW14...
  • Page 70: Troubleshooting In Test Operation

    8-5. Troubleshooting in test operation If there are phenomena such as the output of a check code or the remote controller is not accepted when powered- on after wiring work or during address setup operation, the following causes are considered. 8-5-1.
  • Page 71: Operation From The Indoor Remote Controller Is Not Accepted, And A Check Code Is Displayed On The 7-Segment Display Of The Interface P.c. Board Of The Outdoor Unit

    8-5-2. Operation from the indoor remote controller is not accepted, and a check code is displayed on the 7-segment display of the interface P.C. board of the outdoor unit. Outdoor Indoor remote unit 7- controller segment status display Line addresses and indoor addresses of all the connected Set up addresses.
  • Page 72: In Checking The Number Of Connected Outdoor Units And Connected Indoor Units After

    8-5-4. In checking the number of connected outdoor units and connected indoor units after address setup, a lower number of connected units is displayed. (There are outdoor / indoor units that do not operate in a test operation.) Miswiring of communication lines between indoor units After modification of wiring, set up the addresses again and The number of connected indoor...
  • Page 73: Test Operation Check

    8-6. Test operation check 8-6-1. Fan check START Check code appears Push the Start / Stop button on the remote controller. When a check code has been displayed on the remote controller, remove the cause of the check code, referring to "Check code and check position Check code displayed on remote controller and...
  • Page 74: Cooling / Heating Test Operation Check

    8-6-2. Cooling / Heating test operation check The cooling / heating test operation check can be performed on both the indoor remote controller and the outdoor unit interface P.C. board. (1) Test operation start / stop operation Test operation from the indoor remote controller •...
  • Page 75 Wireless remote controller (4-way Cassette Wireless remote controller (Ceiling type and type) 1-way Cassette SH type) Procedure Operation content Procedure Operation content Start When Temporary button is pushed for 10 seconds or more, “Pi!” sound is heard and Push Temporary operation button. the operation changes to a forced cooling •...
  • Page 76 (2) Test operation START Refer to "Test operation procedure" Test operation for one indoor unit of the indoor remote controller. The operation does not start for approximately 3 minutes after Operation starts powering-on or stopping operation. Note: After powering-on, it may require up to 10 minutes to start the operation due to the initial communications of the system.
  • Page 77 Note 1: Criteria for the difference between suction and discharge temperatures (1) Cooling operation After operating for a minimum of 30 minutes in “COOL” mode, if the T dry bulb temperature difference between suction and discharge air of the indoor unit is 8 °C or more, it is normal. (2) Heating operation After operating for a minimum of 30 minutes in “HEAT”...
  • Page 78: Service Support Function

    8-7. Service support function 8-7-1. Check function for connecting of refrigerant and control lines This function is provided to check misconnection of the refrigerant pipes and the control transmission line (Wiring over lines) between indoor unit and outdoor unit by using the switch on the interface P.C. board of the outdoor unit. However, be sure to check the following items prior to executing this check function.
  • Page 79 Operation start (7-segment display) Press the push-switch SW04 on the interface P.C. board of the outdoor unit for 2 seconds or more. The operation starts. Cooling Operation Check that 7-segment display [B] shows [CC] for Heating cooling and [ HH] for heating. Confirmation of check results (1) (7-segment display) This check operation...
  • Page 80: Function To Start / Stop (On / Off) Indoor Unit From Outdoor Unit

    8-7-2. Function to start / stop (ON / OFF) indoor unit from outdoor unit The following functions of the indoor unit can start or stop by the switches on the interface P.C. board of the outdoor unit. Cooling test Changes the mode of all the [Setup] Section A Section B...
  • Page 81 (1) Cooling test operation function This function is provided to change collectively the mode of all the indoor units connected to the same system for the cooling test operation mode, by using switches on the interface board of the outdoor unit. <Operation procedure>...
  • Page 82 (2) Heating test operation function This function is provided to change collectively the mode of all the indoor units connected to the same system for the heating test operation mode, by using switches on the interface board of the outdoor unit. <Operation procedure>...
  • Page 83 (3) Batch start / stop (ON / OFF) function This function is provided to start / stop collectively all the indoor units connected to the same system by using switches on the interface board of the outdoor unit. <Operation procedure> Be sure to turn on the power at indoor Power ON side before power-ON of outdoor unit.
  • Page 84 (4) Individual start / stop (ON / OFF) individual test operation function This function is provided to start / stop (ON / OFF) individually each indoor unit connected to the same system by using switches on the interface board of the outdoor unit. Set SW01 [16] and set SW02, SW03 to indoor address No.
  • Page 85: Check Code Clearing Function

    8-7-3. Check code clearing function (1)Clearing from the main remote controller Check code clearing in outdoor unit Check code of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which the indoor units operated by the remote controller is connected. (Check code of the indoor unit is not cleared.) For clearing check codes, the service monitor function of the remote controller is used.
  • Page 86 (2)Clearing check code by using switches on the interface board of the outdoor unit Using the switches on the interface P.C. board of the outdoor unit, this function is to clear the currently detected check code for each refrigerant circuit system without resetting the power supply. Check codes in both outdoor and indoor units are once cleared, and check code detection is performed again.
  • Page 87: Remote Controller Distinction Function

    8-7-4. Remote controller distinction function This function is provided to distinguish the remote controller connected to the indoor unit from the outdoor unit for a refrigerant circuit system by using switches on the interface P.C. board of the outdoor unit. <Distinction procedure>...
  • Page 88: Pulse Motor Valve (Pmv) Forced Open / Close Function In Indoor Unit

    8-7-5. Pulse motor valve (PMV) forced open / close function in indoor unit This function is provided to open or close forcedly PMV for 2 minutes in all the indoor units by the switch operation on the interface P.C. board of the outdoor unit. This function is also used to open PMV fully when turning off the power and executing an operation.
  • Page 89 <Operation (PMV4)> [Open fully] Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/7/8], and press SW04 for 2 seconds or more. (7-segment display appears as below.) [**][**P] (View PMV opening degree the “****”) “Open fully” of this model … 500P [Open half] Set the switches SW01/SW02/SW03 on the interface P.C.
  • Page 90: Solenoid Valve Forced Open / Close Function In Outdoor Unit

    8-7-7. Solenoid valve forced open / close function in outdoor unit This function is provided to forcedly open each solenoid valve mounted in the outdoor unit by the switch operation on the interface P.C. board in the outdoor unit. Use this function to check there is no refrigerant clogging with ON / OFF operation of the solenoid valve.
  • Page 91: Fan Operation Check In Outdoor Unit

    8-7-8. Fan operation check in outdoor unit This function is provided to check the fan operation of the outdoor unit by using switches on the interface P.C. board in the outdoor unit. The frequency of the fan speed can be controlled by setting of the switches. Use this function to check the operation or abnormal sound in the fan system.
  • Page 92: Manual Adjustment Function Of Outside Temperature (To) Sensor

    8-7-9. Manual adjustment function of outside temperature (TO) sensor This function is provided to fix TO sensor value manually by the switch operation on the interface P.C. board in the outdoor unit. When the unit stops abnormally due to TO sensor failure, etc, an emergent operation is available by setting up the value manually to position near the current outside temperature.
  • Page 93: Service Support Function List

    8-7-10. Service support function list SW01 SW02 SW03 7-segment di Refrigerant circuit and control communication line check function (Cooling [J . C] operation) Refrigerant circuit and control communication line check function (Heating operation) l l u l l o n i l e l l v i t .
  • Page 94: Monitor Function Of Remote Controller Switch

    8-7-11. Monitor function of remote controller switch When using a remote controller with the model name RBC-AMT32E, the following monitor functions can be used. Calling of service monitor display screen <Content> The sensor temperature or operation status of the remote controller, indoor unit, or the outdoor unit can be known by calling up the service monitor mode from the remote controller.
  • Page 95: Troubleshooting

    Troubleshooting 9-1. Overview (1) Before engaging in troubleshooting (a) Applicable models Indoor units: MM*-AP***, MM*-UP*** Outdoor units: MCY-MHP0806*, MCY-MHP0906*, MCY-MHP1006* (b) Tools and measuring devices required • Screwdrivers (Philips, flat head), spanners, long-nose pliers, nipper, pin to push reset switch, torque drivers (Philips), etc.
  • Page 96: Troubleshooting Method

    9-2. Troubleshooting method The remote controllers (main remote controller and central controller) and the interface P.C. board of an outdoor unit are provided with an LCD display (remote controller) or a 7-segment display (outdoor interface P.C. board) to display operational status. Using this self-diagnosis feature, the trouble site / trouble part may be identified in the event of a trouble by following the method described below.
  • Page 97 (Check code detected by main remote controller) Check code Display of receiving unit Outdoor 7-segment display Indicator light block Main Typical trouble site check code remote Operation Timer Ready Sub-code controller Flash No master remote controller, troubled Signals cannot be received from indoor unit; master –...
  • Page 98 List of Check Codes (Outdoor Unit) List of Check Codes (Outdoor Unit) IPDU: Intelligent Power Drive Unit (Inverter P.C. board) IPDU: Intelligent Power Drive Unit (Inverter P.C. board) : Lighting, : Lighting, : Flashing, : Flashing, : Goes off : Goes off (Check codes detected by outdoor interface - typical examples) (Check codes detected by outdoor interface - typical examples) ALT: Flashing is alternately when there are two flashing LED...
  • Page 99 Check code Display of receiving unit Outdoor 7-segment display TCC-LINK Indicator light block Typical trouble site Description of check code central control or main remote Operation Timer Ready Sub-code controller Flash display Output voltage of high pressure sensor (PD) is zero High pressure sensor (PD) –...
  • Page 100 (Errors detected by IPDU featuring in outdoor unit - typical examples) Check code Display of receiving unit Outdoor 7-segment display Indicator light block TCC-LINK Typical trouble site Description of check code central control or main remote Operation Timer Ready Sub-code Flash controller display...
  • Page 101: Troubleshooting Based On Information Displayed On Remote Controller

    9-3. Troubleshooting based on information displayed on remote controller Using main remote controller (RBC-AMT32E) (1) Checking and testing When a trouble occurs to an air conditioner, a check code and indoor unit No. are displayed on the display window of the remote controller. Check codes are only displayed while the air conditioner is in operation.
  • Page 102 Using TCC-LINK central remote controller (TCB-SC642TLE2) (1) Checking and testing Display of Unit No. Display of check code When a trouble occurs to an air conditioner, a check code and indoor unit No. are displayed on the display window of the remote controller. Check codes are only displayed while the air Alternate blinking conditioner is in operation.
  • Page 103 Using indoor unit indicators (receiving unit light block) (wireless type) To identify the check code, check the 7-segment display on the outdoor unit. To check for check codes not displayed on the 7-segment display, consult the “List of Check Codes (Indoor Unit)” in “9-2. Troubleshooting method”.
  • Page 104 check code Discharge temperature sensor (TD) trouble Operation Timer Ready Heat exchanger temperature sensor (TE) trouble Liquid temperature sensor (TL1, TL3) trouble Outdoor unit temperature sensor Outside air temperature sensor (TO) trouble troubles Alternate blinking Suction temperature sensor (TS1, TS3) trouble Heat sink sensor (TH) trouble Wiring trouble in heat exchanger sensor (TE) and liquid temperature sensor (TL1) Outdoor unit temperature sensor wiring / installation trouble...
  • Page 105 Other (indications not involving check code) check code Operation Timer Ready – Test run in progress Synchronized blinking Operation Timer Ready Setting incompatibility – (automatic cooling / heating setting for model incapable of it and heating setting for cooling-only model) Alternate blinking...
  • Page 106: Check Codes Displayed On Remote Controller And Outdoor Unit (7-Segment Display On I/F Board) And Locations To Be Checked

    9-4. Check codes displayed on remote controller and outdoor unit (7-segment display on I/F board) and locations to be checked For other types of outdoor units, refer to their own service manuals. Check code Location Check code detection Outdoor 7-segment display Description System status Check items (locations)
  • Page 107 Check code Location Outdoor 7-segment display Check code detection Description System status Check items (locations) Main condition(s) detection remote Check Sub-code controller code Remote Duplicated Stop of In two remote controller • Check remote controller controller master remote corresponding configuration (including settings.
  • Page 108 Check code Location Outdoor 7-segment display Check code detection Description System status Check items (locations) Main condition(s) remote detection Check Sub-code controller code Indoor Indoor TCJ Stop of Sensor resistance is infinity • Check connection of TCJ unit sensor trouble corresponding or zero (open / short circuit).
  • Page 109 Check code Location Outdoor 7-segment display Check code detection Description System status Check items (locations) Main condition(s) detection remote Check Sub-code controller code IPDU TH sensor trouble All stop Sensor resistance is zero • Trouble in IGBT built-in (short circuit). temperature sensor –...
  • Page 110 Check code Location Outdoor 7-segment display Check code detection Description System status Check items (locations) Main condition(s) remote detection Check Sub-code controller code IPDU Current All stop Current flow of at least • Check current detection detection circuit specified magnitude is circuit wiring.
  • Page 111 Check code Location Outdoor 7-segment display Check code detection Description System status Check items (locations) Main condition(s) detection remote Check Sub-code controller code No. of priority Duplicated All stop More than one indoor unit • Check displays on priority indoor units priority indoor have been set up as priority indoor unit and outdoor...
  • Page 112 Check code Location Check code detection Outdoor 7-segment display Description System status Check items (locations) Main condition(s) remote detection Check Sub-code controller code Indoor Indoor fan motor Stop of • Check the lock of fan motor – – unit trouble corresponding (AC fan).
  • Page 113 Check code Location Outdoor 7-segment display Check code detection Description System status Check items (locations) Main condition(s) remote detection Check Sub-code controller code • 00: Open phase Detection of All stop Open phase is detected Check for defect in outdoor •...
  • Page 114 Check code Location Outdoor 7-segment display Check code detection Description System status Check items (locations) Main condition(s) remote detection Check Sub-code controller code 01: TS1 All stop Protective shutdown due to • Check for insufficiency in condition leakdetection sustained suction refrigerant quantity.
  • Page 115 Check code Location Check code detection Outdoor 7-segment display Description System status Check items (locations) Main condition(s) remote detection Check Sub-code controller code 0: IGBT IPDU Outdoor fan All stop (Sub code: 0) • Check fan motor. IPDU trouble Fan IPDU over current •...
  • Page 116 Errors detected by TCC-LINK central control device Check code Location Check code detection Outdoor 7-segment display Description System status Check items (locations) Main condition(s) remote detection Sub-code controller TCC-LINK TCC-LINK Continued Central control device is • Check for trouble in central central control operation unable to transmit signal.
  • Page 117 Points to Note When Servicing Compressor (1) When checking the outputs of inverters, remove the wiring from the compressors. How to Check Inverter Output (1) Turn off the power supply. (2) Remove compressor leads from the IPDU P.C. board (A3-IPDU). (Be sure to remove all the leads.) (3) Turn on the power supply and start cooling or heating operation.
  • Page 118: Diagnosis Procedure For Each Check Code

    9-5. Diagnosis procedure for each check code...
  • Page 144: 7-Segment Display Function

    9-6. 7-segment display function 7-segment display on outdoor unit (interface P.C. board) The interface control P.C. board features a 7-segment LED display designed to check operational status. Display items can be changed by changing the combination of the number settings of rotary switches provided on the P.C. board (SW01, SW02 and SW03).
  • Page 145 (1)Display of system information (displayed on outdoor unit) Refrigerant name Display refrigerant name Refrigerant R410A System capacity A [8]~[10]: 8 to 10 HP [HP] Total capacity of indoor units A [i. No. of indoor units connected / A […0.]~[16.]:0 to 16 (No. of units connected) No.
  • Page 146 (2)Display of outdoor unit information (displayed on outdoor unit) Check code B Check code (only latest one displayed) If there is no check code, [– – –] is displayed. If there is sub-code, check code [ ] and sub-code [– ] are displayed alternately, for 3 seconds and 1 second, respectively.
  • Page 147 (3)Display of outdoor cycle data (displayed on outdoor unit) PD pressure data PD pressure (MPaG) is displayed in decimal format. (MPaG: Approx. 10 times magnitude of kg/cm P d. PS pressure data PS pressure (MPaG) is displayed in decimal format. P S.
  • Page 148 (4)Display of indoor unit information (displayed on outdoor unit) Indoor BUS communication signal B Upon receiving signal: [… … 1], Other times: [… … …] receiving status Indoor check code B No check code: [– – –] Indoor HP capacity 0.6 to 10 HP : […0.6] to […10] Indoor request command B [ #.
  • Page 149: Sensor Characteristics

    9-7. Sensor characteristics Outdoor Unit Temperature sensor characteristics Outdoor TS1, TS3, TE, TL1, TL3, and TO sensors Temperature [°C] Resistance [k ] 101.7 76.3 57.7 44.0 33.8 Resistance 26.1 [k ] 20.4 (10 °C or below) Resistance [k ] 16.0 (10 °C or above) 12.6 10.0...
  • Page 150 Outdoor Unit Pressure sensor characteristics • Input / output wiring summary High pressure side (PD) Low pressure side (PS) Pin No. Input / output name Lead wire color Input / output name Lead wire color OUTPUT White — — — —...
  • Page 151 Indoor TC1 sensor Temperature [°C] Resistance [k ] Resistance Resistance [k ] [k ] (10 °C or below) (10 °C or above) Temperature [°C] Indoor TC2 and TCJ sensors Temperature [°C] Resistance [k ] Resistance Resistance [k ] [k ] (10 °C or below) (10 °C or above) Temperature [°C]...
  • Page 152: Pressure Sensor Output Check

    9-8. Pressure sensor output check Outdoor Unit Pd sensor characteristics 0 to 3.92 MPa (0.5 to 4.5 V output for 0 to 3.92 MPa) Voltage readings across pins 1 and 3 of CN501 on I/F P.C. board (with negative-side probe of multimeter placed on pin 3) VOLT VOLT...
  • Page 153 Outdoor Unit Ps sensor characteristics 0 to 0.98 MPa (0.5 to 3.5 V output for 0 to 0.98 MPa) Voltage readings across pins 2 and 3 of CN500 on I/F P.C. board (with negative-side probe of multimeter placed on pin 3) VOLT VOLT VOLT...
  • Page 154: Outdoor Unit Parts Replacement Methods

    Outdoor unit parts replacement methods Step Component Procedure Remarks Common Upper panel WARNING (Front panels, upper panel) Front panel (upper) Do not detach the inverter for 5 minutes after turning off the breaker as doing so may cause electric shocks. Front panel (lower) CAUTION Wear gloves when working on it.
  • Page 155 Step Component Procedure Remarks Discharge 1. Detachment cabinet 1) Remove the front panels and upper panel. Discharge [Step.1] cabinet (upper) 2) Remove the screws of the discharge cabinet (upper), top of the heat exchanger plate. (M4×10, 2) (Fig. 2-1) Heat exchanger (upper) screws (2 positions) Discharge cabinet (lower)
  • Page 156 Step Component Procedure Remarks 2. Attachment Discharge cabinet 1) Mount by reversing the detachment procedure, (continued) attaching the lower and upper discharge cabinets in order. • Insert the hooking tabs into the holes in the motor base and fix each discharge cabinet in place with screws. (Fig. 2-10) Hooking tabs (Fig.
  • Page 157 Step Component Procedure Remarks Side panel 1. Detachment 1) Remove the front panels and upper panel. [Step.1] 2) Remove the screws of the side panel (upper), top of the heat exchanger plate, and side panel Side panel (upper) (lower). (M4×10, 6) (Fig. 3-2) 3) Remove the screws of the side panel (upper) and inverter assembly, and remove the side panel (upper).
  • Page 158 Step Component Procedure Remarks Partition plate WARNING (upper) replacement Do not detach the inverter for 5 minutes after turning off the breaker as doing so may cause Reactor CH-90 electric shocks. Reactor CH-98 Terminal 1. Detachment block 1) Remove the front panels, upper panel and Partition plate discharge cabinets.
  • Page 159 Step Component Procedure Remarks Inverter WARNING assembly Fan motor connector Do not detach the inverter for 5 minutes after (2 positions) turning off the breaker as doing so may cause electric shocks. 1. Detachment 1) Remove the front panels, upper panel, discharge cabinets, side panels, and partition plate (upper).
  • Page 160 Step Component Procedure Remarks Inverter 7) Remove the terminal cover of the compressor, assembly and disconnect the compressor leads from the (continued) compressor. (Fig. 5-5) WARNING If the strap terminal of the compressor lead White line is struck diagonally, it may overheat and cause fire.
  • Page 161 Step Component Procedure Remarks Interface P.C. WARNING board Do not detach the inverter for 5 minutes after turning off the breaker as doing so may cause electric shocks. 1. Detachment 1) Remove the front panels. [Step.1] Disconnect all the connectors on the Interface PC Interface P.C.
  • Page 162 Step Component Procedure Remarks Comp-IPDU WARNING P.C. board Magnetic contactor Do not detach the inverter for 5 minutes after turning off the breaker as doing so may cause PTC thermistor electric shocks. Banding bands 1. Detachment (2 positions) Remove the front panels. [Step.1] Unplug the connector of the sensors, and remove the clamps, etc.
  • Page 163 Step Component Procedure Remarks Fan IPDU 1. Detachment P.C. board 1) Remove the front panels. [Step.1] Unplug the connector of the sensors, and remove the clamps, etc. [“1)” to “5)” of Step.5] Remove the screws of the inverter cover (A), and remove it.
  • Page 164 Step Component Procedure Remarks Fan motor Turn the flange nut clockwise to loosen it. WARNING replacement Do not detach the inverter for 5 minutes after turning off the breaker as doing so may cause electric shocks. 1. Detachment 1) Remove the front panels, upper panel, and discharge cabinets, and fan motor leads.
  • Page 165 Step Component Procedure Remarks Compressor 1. Removing the malfunctioning compressor replacement 1) Collect the refrigerant gas with the recovery equipment. Inverter fixing plate (back) 2) Remove the front panels, upper panel, discharge screws (2 positions) cabinets, side panels, partition plate (upper), and inverter assembly.
  • Page 166 Step Component Procedure Remarks Compressor 12) Burn the connection parts of the SV4 pipe, oil replacement balance pipe (suction pipe side) and discharge (continued) pipe with the burner, and remove. (3 positions) Remove SV4 pipe (Fig. 12-8) CAUTION • Be careful when brazing by the burner to Remove oil balance remove the pipes.
  • Page 167 Step Component Procedure Remarks Compressor 1. Installation of compressor installation 1) Mount the new compressor and secure with the Suction pipe compressor bolts. (Fig. 13-1) Discharge pipe CAUTION Oil balance pipe The tightening torque of the hexagonal bolt to fix the compressor is 11.0 N·m (110 Kgf·cm). Compressor bolts 2) Braze discharge pipe, suction pipe, and oil (3 positions)
  • Page 168 Step Component Procedure Remarks Compressor 4. Installation of sound-insulation mat installation 1) Fix the sound insulation mat (inside) around the (continued) compressor. (Fig. 13-2) 2) Fix the sound insulation mat (outside-1) between Partition plate the partition plate and suction pipe. (Fig. 13-2) 3) Fix the sound insulation mat (outside-2) between Suction pipe the valve fixing plate and the sound insulation...
  • Page 169 Step Component Procedure Remarks PMV1 coil 1. Detachment CN300 PMV4 coil 1) Remove the front panels. (PMV1) [Step.1] CN301 2) Remove the connector connected between the (PMV4) interface P.C. board and PMV coil (PMV1 coil or PMV4 coil). Lead wire clamp CAUTION (1 position)
  • Page 170 Step Component Procedure Remarks Fan guard 1. Detachment Screws (2 positions) Screws (2 positions) 1) Remove the discharge cabinets. [Step.2] CAUTION For scratch protection, work on a carton box, cloth, or the like. 2) Remove the screws from the discharge cabinet and fan guard knob.
  • Page 171 Step Component Procedure Remarks Heat 5) Remove the TO sensor holder , TE sensor holder, exchanger and bindng band to fix it. (Fig. 16-3) Header (upper) assembly 6) Remove the pipe fixing rubber (2 positions), (continued) rubber sheet, and the binding bands. (Fig.16-3) Heat exchanger 4-way (Fig.16-4) valve connection piping 7) Using the burner, remove the header and heat exchanger 4-way valve connecting pipe Remove with the burner (Fig.
  • Page 172 Step Component Procedure Remarks Heat 12) Remove the screws of the condenser coupling exchanger plate and heat exchanger assembly. assembly (M4×10,18) (Fig. 16-5)) (continued) 13) Remove the screws of the bottom plate and heat exchanger assembly. (M4×10, 2) (Fig. 16-6) CAUTION •...
  • Page 173 Step Component Procedure Remarks Handle 1. Detachment (Front panel) 1) Remove the lower part of front panel. [“2)” of Lower part of Step.1] front panel 2) Remove the cushion without tearing it. Cushion (Fig.17-1) 3) Use a flathead screwdriver or something to Reference press on the 3 clamp hooks on the handle and position of remove it.
  • Page 174: C. Board Exchange Procedures

    P.C. board exchange procedures 11-1. Interface P.C. board replacement procedure (MCC-1639:43H69066) 1. Applicable models MCY-MHP0806HT8-(C)(CF) MCY-MHP0906HT8-(C)(CF) MCY-MHP1006HT8-(C)(CF) MCY-MHP0806HS8-(E)(TR) MCY-MHP1006HS8-(E)(TR) 2. Shipped parts list Please make sure that before you do the work, the following parts are shipped all. Parts name Quantity P.C.
  • Page 175: Comp-Ipdu P.c. Board Replacement Procedure (Mcc-1729:43H69065)

    11-2. Comp-IPDU P.C. board replacement procedure (MCC-1729:43H69065) 1. Applicable models MCY-MHP0806HT8-(C)(CF) MCY-MHP0906HT8-(C)(CF) MCY-MHP1006HT8-(C)(CF) MCY-MHP0806HS8-(E)(TR) MCY-MHP1006HS8-(E)(TR) 2. Shipped parts list Please make sure that berore you do the work, the following parts are shipped all. Parts name Quantity P.C.board Replacement Procedure Manual (English 1 page and Chinese1 page A4 paper double side print) Service P.C.board MCC-1729-05C (Comp-IPDU P.C.
  • Page 176: Fan Ipdu P.c. Board Replacement Procedure (Mcc-1728:43H69055)

    11-3. Fan IPDU P.C. board replacement procedure (MCC-1728:43H69055) 1. Applicable models MCY-MHP0806HT8-(C)(CF) MCY-MHP0906HT8-(C)(CF) MCY-MHP1006HT8-(C)(CF) MCY-MHP0806HS8-(E)(TR) MCY-MHP1006HS8-(E)(TR) 2. Shipped parts list Please make sure that before you do the work, the following parts are shipped all. Parts name Quantity P.C.board Replacement Procedure Manual(English and Chinese each 4 page A3 paper double side print.) Service P.C.board MCC-1728-05C(Fan IPDU P.C.board) in Antistatic air cap 3.
  • Page 177 (3) Disconnect all the screws ② and connectors which are connected to the malfunctioning fan IPDU P.C. board. (Since the connectors may be damaged if they are pulled out by grasping their lead wires, be sure to take hold of the connectors themselves when disconnecting them.) (4) Remove the malfunctioning fan IPDU P.C.
  • Page 178: Noise Filter P.c. Board Replacement Procedure (Mcc-1733:43H69057)

    11-4. Noise filter P.C. board replacement procedure (MCC-1733:43H69057) 1. Applicable models MCY-MHP0806HT8-(C)(CF) MCY-MHP0906HT8-(C)(CF) MCY-MHP1006HT8-(C)(CF) MCY-MHP0806HS8-(E)(TR) MCY-MHP1006HS8-(E)(TR) 2. Shipped parts list Please make sure that berore you do the work, the following parts are shipped all. Parts name Quantity P.C. board Replacement Procedure Manual (English and Chinese each 1page A4 paper double side print.) Service P.C.
  • Page 179: Exploded Diagram / Parts List

    Exploded diagram / parts list...
  • Page 180 43H43034 PANEL, ASSY, FRONT, LOWER 43H02007 PANEL, ASSY, SIDE, UP 43H43035 PANEL, ASSY, SIDE, LOWER 43H00020 PANEL, ASSY, TOP 43H19004 GUARD, FAN 43H19014 GUARD, FAN 43H19019 PLATE, STAY 43H07004 GUARD, FIN, SIDE 43H07005 HANDLE 43H15002 MARK, TOSHIBA 43H15004 MARK, TOSHIBA, MiNi-SMMS...
  • Page 181 Inverter assembly PC BOARD ASSY MCC-1639 TK SENSOR TL3 SENSOR TD SENSOR TS SENSOR TO SENSOR HOLDER SENSOR TS3 SENSOR SENSOR HOLDER TE SENSOR TL SENSOR LEAD ASSY,COMPRESSOR TERMINAL (3P,AC600V/30A) SERV-MAG-C0NT SERV-THERMIST0R PC BOARD ASSY MCC-1733 PC BOARD ASSY MCC-1729 PC BOARD ASSY MCC-1728 TERMINAL...
  • Page 182 Q'ty/Set MCY-MHP ****HT8-C(CF) ****HS8-E(TR) Ref.No. Part No. Description 0806 0906 1006 0806 1006 PC BOARD ASSY,INTERFACE,MCC-1639 43H69066 PC BOARD ASSY,NOISE-FILTER,MCC-1733 43H69057 PC BOARD ASSY,COMP-IPDU,MCC-1729 43H69065 PC BOARD ASSY,FAN-IPDU,MCC-1728 43H69055 HOLDER SENSOR(TO) 43H50001 THERMISTOR,PTC 43H53001 LEAD ASSY,COMPRESSOR 43H60029 TERMINAL,4P(AC600V/75A) 43H60002 TERMINAL,3P(AC600V/30A) 43H60016 43H50034 SENSOR,TD...
  • Page 183 For the amount of charge in this example: 0.3 kg/m The possible amount of leaked refrigerant gas in rooms A, (countermeasures B and C is 10kg. needed) The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg. Total amount of refrigerant Toshiba...
  • Page 184 TOSHIBA CARRIER CORPORATION 23-17, TAKANAWAN,3 CHOME,MINATOKU TOKYO, 108-0075, JAPAN Copyright © 1999 to 2012 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved. Revision record First issue Oct. 2011 Revision 1 Change 12.Exploded diagram / Parts list Page 179 to184 2012...

Table of Contents