Check Codes Displayed On Remote Controller And Outdoor Unit (7-Segment Display On I/F Board) And Locations To Be Checked - Toshiba MCY-MHP0305HT-C Service Manual

Air-conditioner (multi type)
Table of Contents

Advertisement

9-4. Check codes displayed on remote controller and
outdoor unit (7-segment display on I/F board) and
locations to be checked
For other types of outdoor units, refer to their own service manuals.
Check code
Location
Outdoor 7-segment display
Main
remote
detection
Check
Sub-code
controller
code
Remote
controller
E01
Remote
controller
E02
Indoor
unit
E03
Indoor
unit
E04
No. of indoor
I/F
units from
which signal is
received
normally
E06
E06
I/F
E07
Duplicated
Indoor
indoor address
unit
I/F
E08
E08
of
Description
System status
Indoor-remote
Stop of
controller
corresponding
communication
unit
error
(detected at
remote
controller end)
Remote
Stop of
controller
corresponding
transmission
unit
error
Indoor-remote
Stop of
controller
corresponding
communication
unit
error
(detected at
indoor end)
Indoor-outdoor
Stop of
communication
corresponding
circuit error
unit
(detected at
indoor end)
Dropping out of
All stop
indoor unit
Indoor-outdoor
All stop
communication
circuit error
(detected at
outdoor end)
Duplicated
All stop
indoor address
95
118
Error detection
Check items (locations)
condition(s)
Communication between
• Check remote controller
indoor P.C. board and remote
inter-unit tie cable (A / B).
controller is disrupted.
• Check for broken wire or
connector bad contact.
• Check indoor power
supply.
• Check for defect in indoor
P.C. board.
• Check remote controller
address settings
(when two remote
controllers are in use).
• Check remote controller
P.C. board.
Signal cannot be transmitted
• Check internal
from remote controller to
transmission circuit of
indoor unit.
remote controller.
--- Replace remote
controller as necessary.
There is no communication
• Check remote controller
from remote controller
and network adaptor
(including wireless) or
wiring.
network adaptor.
Indoor unit is not receiving
• Check order in which
signal from outdoor unit.
power was turned on for
indoor and outdoor units.
• Check indoor address
setting.
• Check indoor-outdoor tie
cable.
• Check outdoor termination
resistance setting (SW30,
Bit 2).
Indoor unit initially
• Check power supply to
communicating normally fails
indoor unit.
to return signal for specified
(Is power turned on?)
length of time.
• Check connection of
indoor-outdoor
communication cable.
• Check connection of
communication connectors
on indoor P.C. board.
• Check connection of
communication connectors
on outdoor P.C. board.
• Check for defect in indoor
P.C. board.
• Check for defect in outdoor
P.C. board (I/F).
Signal cannot be transmitted
• Check outdoor termination
from outdoor to indoor units
resistance setting (SW30,
for 30 seconds continuously.
Bit 2).
• Check connection of
indoor-outdoor
communication circuit.
More than one indoor unit is
• Check indoor addresses.
assigned same address.
• Check for any change
made to remote controller
connection (group /
individual) since indoor
address setting.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents