Toshiba MCY-MHP0305HT-C Service Manual page 103

Air-conditioner (multi type)
Table of Contents

Advertisement

Check code
Location
Outdoor 7-segment display
Main
remote
detection
Check
Sub-code
controller
code
I/F
P05
P05
IPDU
I/F
P07
P07
Detected
Indoor
indoor address
unit
P10
P10
Indoor
unit
P12
I/F
P13
P13
of
Description
System status
Inverter DC
All stop
voltage (Vdc)
error
(compressor)
Heat sink
All stop
overheating
error
Indoor overflow
All stop
error
Indoor fan motor
Stop of
error
corresponding
unit
Outdoor liquid
All stop
backflow
detection error
102
124
Error detection
Check items (locations)
condition(s)
Inverter DC voltage is too
Check for defect in outdoor
high (overvoltage) or too
P.C. board (IPDU).
low (undervoltage).
Check for defect in outdoor
power supply wiring.
Temperature sensor built into
Check power supply
IGBT (TH) is overheated.
voltage.
Check outdoor fan system
error.
Check heat sink cooling
duct for clogging.
Check IGBT and heat sink
for thermal performance for
faulty installation.
(e.g. mounting screws and
thermal conductivity)
Check for defect in IPDU.
(faulty IGBT built-in
temperature sensor (TH))
Float switch operates.
Check float switch
Float switch circuit is open-
connector.
circuited or disconnected
Check operation of drain
at connector.
pump.
Check drain pump circuit.
Check drain pipe for
clogging.
Check for defect in indoor
P.C. board.
Motor speed
Check connection of fan
measurements
connector and wiring.
continuously deviate from
Check for defect in fan
target value.
motor.
Overcurrent protection is
Check for defect in indoor
activated.
P.C. board.
Check impact of outside air
treatment (OA).
<During heating operation>
Check full-close operation
When system is in heating
of outdoor PMV.
operation, outdoor PMV 1
Check for defect in Pd or
continuously registers
Ps sensor.
opening of 100 p or less while
Check gas balancing
under SH control.
circuit (SV2) for clogging.
Check defect in outdoor
P.C. board (I/F).
Check capillary of oil
separator oil return circuit
for clogging.
Check for leakage of check
valve in discharge pipe
convergent section.