Toshiba MCY-MHP0305HT-C Service Manual page 78

Air-conditioner (multi type)
Table of Contents

Advertisement

(2)Clearing error by using switches on the interface board of the outdoor unit
Using the switches on the interface P.C. board of the outdoor unit, this function is to clear the currently detected
error for each refrigerant circuit system without resetting the power supply.
Errors in both outdoor and indoor units are once cleared, and error detection is performed again.
Set the rotary switches on the interface P.C. board of the
outdoor unit as follows.
Set SW01 / SW02 / SW03 to [2/16/1]
Press the push-switch SW04 on the same board for
5 to 10 seconds.
[ C L] is displayed in 7-segment display [B] on the board
(for 5 seconds), and the error is completely cleared.
Interface P.C. board
SW06
SW07
SW09
SW10
SW11
SW12 SW13
SW14
SW16
SW17
SW30
(3)Clearing error by resetting power
This function is provided to clear error in a system by resetting the power of all the outdoor and the indoor units.
As same as the clearing method by the interface P.C. board, errors of both the outdoor and the indoor units are
once cleared, and error detection is performed again.
<Method>
(1) Be sure to reset power of both the outdoor and the indoor units.
(2) Turn on the power of the indoor unit prior to the power of the outdoor unit.
NOTE)
After power reset, it requires usually 3 minutes to power-on due to the initial communication of the
system. In some cases, it requires max. 10 minutes.
SW04
SW05
SW15
Push switch
D600 D601 D602 D603 D604
SW01
SW02
SW03
7-segment
display [A]
77
100
7-segment display
.
7-segment display
.
.
Push switch
SW04
SW05
SW15
7-segment
display [B]
D600 D601 D602 D603 D604
SW01
SW02
SW03
Rotary switches

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents