Variable Speed Drive (Vsd) Details Screen - York YK-EP Operation And Maintenance Manual

Centrifugal chiller
Hide thumbs Also See for YK-EP:
Table of Contents

Advertisement

Variable Speed Drive (VSD) details screen

Figure 40: VSD details screen
This screen displays more detailed information pertaining to a Variable Speed Drive (VSD) part
number 371-03789-xxx (503HP 60Hz; 419HP 50Hz).
Note: Requires a login access level of SERVICE.
Table 110: Display only
Field/LED
Access level
name
Motor Run
(LED)
Motor
Current %
Full Load
Amps
Current Limit
Setpoint
Pulldown
Demand
Time Left
Water Pump
Output (LED)
YK-EP Style B Centrifugal Chiller
Description
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Displays the motor current as a percentage of the Full Load Amps
(FLA) value. For the Variable Speed Drive this is the data returned by
the VSD Logic Board.
Displays the current limit value in use. This value could come from
a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input in Analog
Remote mode, PWM signal in Digital Remote mode, E-Link or SC-
EQ communications interface in ISN mode, or a locally programmed
value.
Displays the time remaining in the programmed pulldown period if
the value is nonzero.
Indicates whether the relay controlling the water pump output is
energized.
111

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

160.87-om1

Table of Contents