Economizer compressor screen

Figure 14: Economizer compressor screen
This screen displays a cutaway view of the Economizer compressor, revealing the impeller, and
shows all conditions associated with the compressor. In addition, with the proper access level,
the Pre-Rotation Vanes may be manually controlled. Animation of the compressor impeller
indicates whether the chiller is presently in a RUN condition. This screen also serves as a gateway to
subscreens for calibrating the Pre-Rotation Vanes, calibrating the Proximity Probe, configuring the
Hot Gas Bypass, or providing advanced control of the Compressor Motor Variable Speed Drive.
Table 29: Display only
Field/LED
Access level
name
Oil Pump
Drive
Command
Frequency
Discharge
Temperature
Discharge
Superheat
High Speed
Thrust
Bearing Limit
Switch LED
Pre-Rotation
Vanes
Opening LED
46
Description
Displays the command frequency of the Oil Pump Drive. The
frequency will go up or down to match the pump motor output to
the required oil pressure.
Displays the temperature of the refrigerant in its gaseous state at
discharge of the compressor as it travels to the condenser.
Displays the discharge superheat, calculated as (Discharge
Temperature – Condenser Saturation temperature).
Displays when the high-speed thrust bearing limit switch is
activated.
Displays when the Economizer PRV is opening.
YK-EP Style B Centrifugal Chiller