Requirements
The supply voltage to the interface module must be switched on.
Required tool
3 to 3.5 mm screwdriver (for resetting via the RESET button)
Procedure
1. Remove the interface module from the mounting rail and swivel it downwards.
2. The RESET button is located on the back of the interface module behind a small opening:
Push a screwdriver into the small opening, thus pressing the RESET button.
3. Release the RESET button.
4. Press the RESET button for another 3 seconds.
5. Look at the LED display of the interface module to see whether the reset was successful:
RUN LED flashes for 3 seconds, ERROR and MAINT LED are off.
6. Install the interface module back on the mounting rail.
7. Configure the interface module again.
Equipment Manual IM 155-6 PN HF, Edition 12/2015
Section 3.1 Pin assignment
PROFINET interface X1 Port 2:
If autonegotiation is disabled, the RJ-45 socket (X1 Port 2) has the switch assignment
(MDI-X).
Equipment Manual IM 155-6 PN HS, Edition 09/2016
Section 3.1 Pin assignment
PROFINET interface X1 Port 2:
If autonegotiation is disabled, the RJ-45 socket (X1 Port 2) has the switch assignment
(MDI-X).
Section 7 Technical specifications
• The PROFINET certification of network Class 3 is in preparation.
• Technical specifications of the BusAdapters BA 2×SCRJ, BA SCRJ/RJ45, BA SCRJ/FC:
The maximum length of the PCF-GI fiber-optic cable is 250 m.
Product information on the documentation of the ET 200SP distributed I/O system
Product Information, 02/2021, A5E03799595-BG
Supplements to ET 200SP documentation
2.4 Interface module manuals