Line/Load Connection - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line connection
4.6 Wideband Line Filter for Active Line Modules
4.6.3.1

Line/load connection

Table 4-9
Type of connection
Terminals
Line supply connection (line supply)
Load connection (load)
Wideband Line Filter for Active Line Modules
16 kW
36 and 55 kW
80 kW
120 kW
1) for ring cable lugs to DIN 46234
54
Designations
L1, L2, L3, PE
U, V, W
Screw terminal: 10 mm
3-pin/1.5 -1.8 Nm (see Screw Terminals chapter)
2
Grounding stud: M5/3 Nm
Screw terminal: 50 mm
3-pin/6 - 8 Nm (see Screw Terminals chapter)
2
Grounding stud: M8/13 Nm
Screw terminal: 95 mm
3–pin/15 - 20 Nm (see Screw Terminals chapter)
2
Grounding stud: M8/13 Nm
Connection strap: d = 11 mm (M10/25 Nm)
Grounding stud: M8/13 Nm
Note: No shock-hazard protection (IP00B acc. to 60529)
1)
1)
1)
1)
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4