Meaning Of The Leds On The Control Supply Module - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

The Control Supply Module (CSM) is connected to the line supply (3-ph. 380 V AC –10 % up
to 480 V +10 %) via the appropriate screw terminals (0.2 to 4 mm
preferably be made without using an isolating device (e.g. contactor).
The CSM is protected corresponding to the data provided in the Equipment Manual for
Booksize power units. The CSM has an internal line filter (Class A for TN line supplies), and
the pre-charging circuit for the DC link inside the unit is electrically isolated from the 24 V
supply.
Note
When engineering the line supply of the CSM, it should be noted that the CSM may not be
connected to the line supply after the line module is connected to the line supply. When
charging, this prevents the DC link from being immediately loaded by the CSM.
NOTICE
If a selectively tripping AC/DC-sensitive residual-current circuit-breaker is used, the Control
Supply Module must be connected downstream of this.
11.3.3.3

Meaning of the LEDs on the Control Supply Module

Table 11-8
Control Supply Module - Description of the LEDs
LED
Color
READY
-
Green
DC LINK
-
Yellow
Red
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4
State
Description
Off
Electronics power supply outside the permissible tolerance range.
Steady light
Ready for operation. Output voltage within tolerance range.
Off
DC input voltage < 290 V
Steady light
DC input voltage in the range 370 < Ue < 820 V
operation possible
Steady light
DC input voltage outside the tolerance range.
DC input voltage 290 V< Ue < 370 V or Ue > 820 V
DC link components
11.3 Control Supply Module
). This connection should
2
, floating operation not possible
DC
DC
Floating
DC
239