Line Connection Via A Ground-Fault Circuit Interrupter - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line connection
4.13 Line connection variants
4.13.5

Line connection via a ground-fault circuit interrupter

In addition to the implemented protective measures against direct and indirect contact,
selectively tripping AC/DC-sensitive residual-current circuit-breakers (Type B) can be used.
Residual-current circuit-breakers alone are not permissible to provide protection against
direct and indirect contact.
Note
Operation behind residual-current circuit-breakers is currently only possible with the 5 kW,
10 kW, 16 kW, 20 kW and 36 kW Line Modules.
Figure 4-44
106
DANGER
Residual-current circuit-breaker (RCCB)
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4