X1 Functional Ground - Siemens SINAMICS S120 Equipment Manual

Booksize cold-plate power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

DC link components
11.4 Voltage Clamping Module (VCM)
Figure 11-15 Circuit diagram: Voltage Clamping Module
11.4.3.2

X1 functional ground

X1 functional ground
To ensure that the Voltage Clamping Module functions properly, a functional ground must be
connected to X1. Please note:
● The cables must be routed via the shortest possible path
● Cross-section: 4 mm² to 16 mm²
● When a line filter is used, the functional ground should be located on the metallic
● In systems without a line filter, it should be connected on the PE busbar.
246
installation panel in the immediate vicinity of the line filter.
Booksize cold-plate power units
Manual, (GH4), 03.2007, 6SL3097-2AJ00-0BP4

Advertisement

Table of Contents
loading

Table of Contents