3.3 Technical specifications

3.3
Technical specifications
Unless specified otherwise, the following technical data is valid for all the following
components of the air-cooled SINAMICS S120 drive system.
Table 3- 1
General technical data
Electrical data
Line supply voltage
Line frequency
Output voltage
Output frequency
Electronic power supply
Maximum short-circuit current I
ing to IEC, in conjunction with the speci-
fied fuses or circuit breakers for devices in
the Chassis format
Maximum short-circuit current I
ing to IEC, in conjunction with the speci-
fied fuses or circuit breakers for devices in
the Chassis-2 format
Rated short-circuit current SCCR (Short-
Circuit Current Rating) according to
UL508C (up to 600 V), in conjunction with
the specified fuses or circuit breakers
Rated short-circuit current SCCR (Short-
Circuit Current Rating) according to
UL61800-5-1, in conjunction with the
specified fuses or circuit breakers for de-
vices in the Chassis-2 format
Frequency with which the DC link is pre-
charged
Overvoltage category
Electromagnetic compatibility (EMC)
Emitted interference
Standard
With line filter
Noise immunity
36
3 AC 380 V -10% (-15% < 1 min) ... 3 AC 480 V +10%
3 AC 500 V -10% (-15% < 1 min) ... 3 AC 690 V +10%
47 ... 63 Hz
0 to line connection voltage, depending on the type of infeed.
With an Active Line Module, it is also possible to achieve a higher output volt-
age.
Vector control: 0 ... 550 Hz
Servo control: 0 ... 550 Hz
U/f control: 0 ... 550 Hz
24 VDC (20.4 V ... 28.8 V)
implemented as PELV circuit according to EN 61800-5-1
Ground = Negative polarity grounded via the electronics
accord-
1.1 ... 447 kW: 65 kA
CC
448 ... 671 kW: 84 kA
672 ... 1193 kW: 170 kA
>1194 kW: 200 kA
accord-
100 kA
CC
1.1 ... 447 kW: 65 kA
448 ... 671 kW: 84 kA
672 ... 1193 kW: 170 kA
>1194 kW: 200 kA
100 kA
Max. 1 precharge every 3 minutes
Class III according to EN 61800-5-1
Category C3 (second environment) according to EN 61800-3
Category C2 (first
When used in the first environment, an appropriately trained and authorized
*)
technical person must set up the drive and commission it.
NOTE: An appropriately trained and authorized technician is person or organi-
zation with the required experience for setting up and/or for commissioning
the drive systems, including the associated EMC aspects.
Use in the first and second environment according to EN 61800-3
1)
1)
1)
and second environments) according to EN 61800-3
*)
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3