Technical Specifications - Siemens SINAMICS S120 Equipment Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

1.3

Technical specifications

Technical specifications
Unless specified otherwise, the following technical specifications are valid for all the following
components of the SINAMICS S120 drive system.
Table 1- 1
General technical specifications
Electrical data
Line connection voltage
Line frequency
Output voltage
Output frequency
Electronic power supply
Short-circuit current rating SCCR in
accordance with UL508C (up to 600 V)
DC link precharging frequency
Interference suppression
Standard
With line filter
Overvoltage category
Mechanical data
Vibratory load
Transport
1)
Operation
Shock stressing
Transport
1)
Operation
Ambient conditions
Degree of protection
Protection class
Shock protection
Permissible ambient and coolant
temperature (air) during operation for line-
side components, Line Modules and
Motor Modules
Chassis power units
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3
3-ph. 380 V AC -10% (-15% < 1 min) to 3-ph. 480 V AC +10%
3-ph. 500 V AC -10% (-15% < 1 min) to 3-ph. 690 V AC +10%
47 Hz to 63 Hz
0 to line connection voltage, depending on the type of infeed.
With an Active Line Module, it is also possible to achieve a higher output
voltage.
0 Hz to 300 Hz
24 V DC (20.4 V - 28.8 V)
1.1 kW – 447 kW: 65 kA
448 kW – 671 kW: 84 kA
672 kW – 1193 kW: 170 kA
>1194 kW: 200 kA
Maximum of one precharge every 3 minutes
Category C3 (environment 2) to EN 61800-3
Category C2 (environment 1) to EN 61800-3
Class III to EN 60664-1
EN 60721-3-2, class 2M2
Test values in accordance with EN 60068-2-6 test Fc:
10 to 58 Hz with constant deflection = 0.075 mm
58 to 150 Hz with constant acceleration = 9.81 m/s² (1 g)
EN 60721-3-2, class 2M2
Test values in accordance with EN 60068-2-27 test Ea: 98 m/s² (10 g) /
20 ms
IP00 or IP20 to EN 60529
Class I (with protective conductor system) and class III (PELV) to EN 61800-5-1
DIN VDE 0100 Part 100 and BGV A 3 when used properly
0 °C to +40 °C without derating,
>40 °C to +55 °C (see derating characteristics)