7.6 E: Motor Parameters

7.6

E: Motor Parameters

E1: V/f Pattern for Motor 1
No.
Name
(Hex.)
E1-01
Input AC Supply Voltage
(0300)
E1-03
V/f Pattern Selection
(0302)
E1-04
Maximum Output Frequency Sets the maximum output frequency for the V/f pattern.
(0303)
E1-05
Maximum Output Voltage
(0304)
E1-06
Base Frequency
(0305)
E1-07
Mid Point A Frequency
(0306)
E1-08
Mid Point A Voltage
(0307)
E1-09
Minimum Output Frequency Sets the minimum output frequency for the V/f pattern.
(0308)
E1-10
Minimum Output Voltage
(0309)
E1-11
Mid Point B Frequency
(030A)
Expert
E1-12
Mid Point B Voltage
(030B)
Expert
E1-13
Base Voltage
(030C)
Expert
188
Sets the drive input voltage.
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you can make a
custom pattern.
0 : Const Trq, 50Hz base, 50Hz max
1 : Const Trq, 60Hz base, 60Hz max
2 : Const Trq, 50Hz base, 60Hz max
3 : Const Trq, 60Hz base, 72Hz max
4 : VT, 50Hz, 65% Vmid reduction
5 : VT, 50Hz, 50% Vmid reduction
6 : VT, 60 Hz, 65% Vmid reduction
7 : VT, 60Hz, 50% Vmid reduction
8 : High Trq, 50Hz, 25% Vmin boost
9 : High Trq, 50Hz, 65% Vmin boost
A : High Trq, 60Hz, 25% Vmin boost
B : High Trq, 60Hz, 65% Vmin boost
C : High Freq, 60Hz base, 90Hz max
D : High Freq, 60Hz base, 120Hz max
E : High Freq, 60Hz base, 180Hz max
F : Custom
Note:
• Set the correct V/f pattern for the application and operation area. An incorrect V/f pattern can
decrease motor torque and increase current from overexcitation.
• Parameter A1-03 [Initialize Parameters] will not initialize the value of E1-03.
Sets the maximum output voltage for the V/f pattern.
Sets the base frequency for the V/f pattern.
Sets a middle output frequency for the V/f pattern.
Sets a middle output voltage for the V/f pattern.
Sets the minimum output voltage for the V/f pattern.
Sets a middle output frequency for the V/f pattern.
Sets a middle point voltage for the V/f pattern.
Sets the base voltage for the V/f pattern.
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Description
Default
(Range)
208/240 V: 240 V,
480 V: 480 V
(208/240 V: 155 - 255 V,
480 V: 310 - 510 V)
F
(0 - F)
60.0 Hz
(40.0 to 400.0 Hz)
208/240 V: 230.0 V,
480 V: 460.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
60.0 Hz
(0.0 - E1-04)
30.0 Hz
(0.0 - E1-04)
Determined by o2-04
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
1.5 Hz
(Determined by E1-04)
10.2 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
0.0 Hz
(0.0 - E1-04)
0.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
0.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)