Getting Started
SM 322: Short Circuit to L+
1. Open the front door of the DO module and use a wire to short-circuit the digital
output 0 (terminal 3) to L+ (terminal 1).
2. Watch the status LEDs.
IM 153-2:
– SF: comes on
SM 322; DO 8 x 24 V DC/0.52 A:
– SF: comes on ⇒ Diagnostic message has been issued
comes on ⇒ Channel error
– F0:
– 0:
Off
3. Evaluate the diagnostic message.
Result:
– Station status 1:
diagnostics
– Module diagnosis
– Channel-specific diagnosis:
Byte (x+16).0 to (x+16).5:
Byte (x+17).0 to (x+17).5:
Byte (x+18).0 to (x+18).4:
4. Remove the wire between terminal 3 and terminal 1.
Evaluate the diagnostic LEDs again.
IM 153-2:
– SF: Off
SM 322; DO 8 x 24 V DC/0.52 A:
– SF: Off
– F0:
Off
– 0:
On
The diagnostic message is erased.
2-12
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
⇒ Output is not active
Byte x.3 is set
Byte (x+7).4 is set
000100
B
000000
B
00001
B
⇒ External
⇒ Slot 5
⇒ Slot 5
⇒ Channel 0
⇒ Short circuit
Distributed I/O Device ET 200M