Electrical Data; Typical Field Control Wiring Diagram 2 Stage Thermostat; Typical Field Power Wiring Diagram - York R-410A Installation Manual

R-410a affinity series 2-5 ton
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

288429-YIM-A-0307
** = Minimum wire size of 18 AWG
wire should be used for all field
installed 24 volt wire.
PROGRAMMABLE
THERMOSTAT ONLY
Figure 8: Typical Field Control Wiring Diagram 2 Stage Thermostat
Figure 9: Typical Field Power Wiring Diagram
Table 5: Electrical Data
Size
Model
Volt
(Tons)
024
DEX
208/230-1-60 10.2
(2.0)
030
DEX
208/230-1-60 14.1
(2.5)
208/230-1-60 16.6
036
DEX
(3.0)
208/230-3-60 11.1
460-3-60
Unitary Products Group
2 STAGE
THERMOSTAT
R
G
Y
1
Y
2
W
C
OD Fan
Supply
Compressors
Motors
Blower
(each)
(each)
RLA LRA
MCC
FLA
52
16
1.2
70
22
1.2
82
26
1.2
58
17
1.2
4.5
29
7
0.8
UNIT CONTROL BOARD
TERMINAL STRIP
* *
R
G
Y
1
Y/Y
2
W
2
W
1
C
Electric Heat Option
Motor
FLA
Model
kW
None
-
2NH04500506
3.8/5
4.3
2NH04500706 5.6/7.5
2NH04501006 7.5/10
None
-
2NH04500506
3.8/5
4.3
2NH04500706 5.6/7.5
2NH04501006 7.5/10
2NH04501506 11.3/15
None
-
2NH04500506
3.8/5
4.3
2NH04500706 5.6/7.5
2NH04501006 7.5/10
2NH04501506 11.3/15
None
-
4.3
2NH04501025 7.5/10
2NH04501525 11.3/15
None
-
4.3
2NH04501046
10
2NH04501546
15
NOTE: HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.
24 VOLT
TRANSFORMER
1
MCA
(Amps)
Stages
Amps
-
-
18.3
1
18.1/20.8
40.8/44.3
2
27.1/31.3
52.1/57.3
2
36.1/41.7
63.4/70.3
-
-
23.1
1
18.1/20.8
45.7/49.2
2
27.1/31.3
57/62.2
2
36.1/41.7
68.3/75.2
2
54.2/62.5
90.8/101.3
-
-
26.3
1
18.1/20.8
48.8/52.3
2
27.1/31.3
60.1/65.3
2
36.1/41.7
71.4/78.3
2
54.2/62.5
94/104.4
-
-
19.4
1
20.8/24.1
45.4/49.4
1
31.3/36.1
58.5/64.5
-
-
10.7
1
12
25.7
1
18
33.2
2
Max Fuse
/
3
Breaker
Size
(Amps)
25
45/45
60/60
70/80
30
50/50
60/70
70/80
100/110
35
60/60
70/70
80/80
100/110
25
50/50
60/70
15
30
35
9