Table 6-2 - Simplicity Elite Data Map - York ECO2 YPAL 050 Installation & Operation Manual

Design level f simplicity elite control
Hide thumbs Also See for ECO2 YPAL 050:
Table of Contents

Advertisement

User Interface Control Center

TABLE 6-2 - SIMPLICITY ELITE DATA MAP

Writing to any register not in this list
may cause erratic operation
ADDRESS
ADDRESS
BIT
(HEX)
(DEC)
00 H
0 H
NA
00 L
0 L
NA
01 H
1 H
NA
0
1
2
3
4
5
6
7
01 L
1 L
NA
02 H
2 H
NA
02 L
2 L
NA
03 H
3 H
NA
03 L
3 L
NA
04 L
4 L
NA
05 H
5 H
NA
05 L
5 L
NA
06 H
6 H
NA
06 L
6 L
NA
07 H
7 H
NA
07 L
7 L
NA
08 H - 14 L
8 H - 20 L
NA
15 H
21 H
NA
0
1
2
3
4
130
INITIAL/
DEFAULT
MIN
MAX
VALUE
VALUE
VALUE
(HEX)
20
NA
NA
-
0
255
54
-
-
NA
NA
NA
30
0
30
60
0
255
0
0
30
30
0
255
3
1
10
0
0
255
0
0
255
0
0
255
0
0
255
0
0
255
0
0
255
-
-
-
This product is not designed to accept
continuous writes to data stored in
long term memory. It is recommended
that no stored value be changed more
often than an average of once per
hour. Changing data more often risks
damaging the ability of the control to
store new data for the full life of the
product.
DESCRIPTION
DEVICE ID = 20 FOR ELITE
DEVICE SOFTWARE REVISION
OPTION BYTE #1
BITS 1 AND 0 = 0,0 RESPECTIVELY THERE ARE 0 STAGES OF
HEAT; 0,1 = 1 STAGE; 1,0 = 2 STAGES; 1,1 = 3 STAGES
1 = HEATING MODE ENABLED FOR OPERATION
1 = TURN OFF CONTINUOUS FAN WHEN STARTING HEAT
1 = COOLING MODE ENABLED FOR OPERATION
1 = ECONOMIZER LOADING ACTIVE
1 = SPACE SENSOR FAULT OVERRIDE ENABLED
NA
ACTIVE ALARM
FAN ON DELAY FOR HEAT (SECONDS)
FAN OFF DELAY FOR HEAT (SECONDS)
FAN ON DELAY FOR COOL (SECONDS)
FAN OFF DELAY FOR COOL (SECONDS)
MINIMUM RUN TIME FOR COMPRESSORS (MINUTES)
HEATING #1 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)
HEATING #1 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
HEATING #2 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)
HEATING #2 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
HEATING #3 ACCUMULATED RUN TIME (HOURS, HIGH BYTE)
HEATING #3 ACCUMULATED RUN TIME (HOURS, LOW BYTE)
REGISTERS 8 - 20 STORE THE UNIT NAME. WHEN WRITTEN,
ALL 13 REGISTERS (AT 2 BYTES PER REGISTER) SHOULD BE
WRITTEN. THE FORMAT IS ASCII. CHARACTER #1 IS IN 8 H.
CHARACTER #2 IS IN 8 L. CHARACTER #3 IS IN 9 H, AND SO ON.
INPUT STATUS BYTE #1
1 = Y1 ON (COOLING 1ST STAGE)
1 = Y2 ON (COOLING 2ND STAGE)
1 = Y3 ON (COOLING 3RD STAGE)
1 = Y4 ON (COOLING 4TH STAGE)
1 = W1 ON (HEATING 1ST STAGE)
FORM 100.50-NOM6 (1207)
Continued on next page
JOHNSON CONTROLS