Table 6-1 - Parameter Points List - York ECO2 YPAL 050 Installation & Operation Manual

Design level f simplicity elite control
Hide thumbs Also See for ECO2 YPAL 050:
Table of Contents

Advertisement

TABLE 6-1 - PARAMETER POINTS LIST

ADDRESS
NUMBER
1
RUN TEST
2
HEAT FAN ON DELAY
3
HEAT FAN OFF DELAY
4
COOL FAN ON DELAY
5
COOL FAN OFF DELAY
6
ADDRESS
7
TURN OFF CONTINUOUS FAN WHEN STARTING
8
CONSTRUCTION MODE
9
UNOCCUPIED OVERRIDE TIME PERIOD
10
CV OCCUPIED COOLING SETPOINT
11
CV OCCUPIED HEATING SETPOINT
12
CV UNOCCUPIED COOLING SETPOINT
13
CV UNOCCUPIED HEATING SETPOINT
14
SUPPLY AIR TEMP LIMIT FOR COOLING ENABLE
15
SUPPLY AIR TEMP LIMIT COOLING SETPOINT
16
SUPPLY AIR TEMP LIMIT FOR HEATING ENABLED
17
SUPPLY AIR TEMP LIMIT HEATING SETPOINT
18
HYDRONIC HEATING ENABLED
HYDRONIC HEATING STAGE #1 SUPPLY AIR
19
SETPOINT
HYDRONIC HEATING STAGE #2 SUPPLY AIR
20
SETPOINT
HYDRONIC HEAT ACTUATOR VALVE REVERSE
21
ACTING
REMOTE CONTROL INPUT ENABLE FOR THIRD
22
PARTY BAS
VAV COOLING SUPPLY AIR TEMP UPPER
23
SETPOINT
VAV COOLING SUPPLY AIR TEMP LOWER
24
SETPOINT
25
VAV SUPPLY AIR TEMP RESET SETPOINT
26
VAV OCCUPIED HEATING ENABLED
27
VAV OCCUPIED HEATING SETPOINT
28
MORNING WARM-UP ENABLE
MORNING WARM-UP / VAV RETURN AIR TEMP
29
SETPOINT
30
DUCT PRESSURE SETPOINT
31
BUILDING PRESSURE SETPOINT
32
ECONOMIZER INSTALLED
33
ECONOMIZER FIRST STAGE SETPOINT
34
ECONOMIZER SECOND STAGE SETPOINT
35
ECONOMIZER MINIMUM POSITION
JOHNSON CONTROLS
DESCRIPTION
UNITS OF ADJUSTMENT
PARAMETER BIT
SECONDS
SECONDS
SECONDS
SECONDS
DATA
PARAMETER BIT
PARAMETER BIT
DATA MINUTES
DEGREES F
DEGREES F
DEGREES F
DEGREES F
PARAMETER BIT
DEGREES F
PARAMETER BIT
DEGREES F
PARAMETER BIT
DEGREES F
DEGREES F
PARAMETER BIT
PARAMETER BIT
DEGREES F
DEGREES F
DEGREES F
PARAMETER BIT
DEGREES F
PARAMETER BIT
DEGREES F
PRESSURE - INCHES OF
H2O
PRESSURE - INCHES OF
H2O
PARAMETER BIT
DEGREES F
DEGREES F
PERCENT
FORM 100.50-NOM6 (1207)
RANGE OF
CURRENT
ADJUSTMENT
SETTING
0 = OFF, 1 = ON
OFF
0-30
30
0-255
60
0-30
0
0-255
30
1-250
1
0 = OFF, 1 = ON
OFF
0 = OFF, 1 = ON
OFF
0-240
60
0 = DISABLED
MINUTES
45º - 99º
72º
45º - 99º
68º
45º - 99º
85º
45º - 99º
60º
0 = OFF, 1 = ON
ON
40º - 65º
50º
0 = OFF, 1 = ON
ON
100º - 180º
135º
0 = OFF, 1 = ON
OFF
80º - 180º
120º
80º - 180º
150º
0 = OFF, 1 = ON
OFF
0 = OFF, 1 = ON
OFF
40º - 70º
60º
40º - 70º
55º
40º - 85º
72º
0 = OFF, 1 = ON
OFF
40º - 85º
68º
0 = OFF, 1 = ON
ON
50º - 85º
70º
0.000 - 5.000
1.500
-.250 -.250
0.1
0 = OFF, 1 = ON
ON
40º - 65º
55º
40º - 65º
50º
0 - 100%
20%