Judgment Output Reading; External Input - Panasonic SC-HG1-C User Manual

Cc-link communication unit for digital displacement sensors
Table of Contents

Advertisement

CC-LINK Network Communication

4-6 Judgment output reading

You can get the external output and alarm output of each controller by reading RX[20] to [2E],
RX[30] to [3E], RX[40] to [4E], and RX[50] to [5E] in the memory map.
These values are always kept updated to the most recent state, so operations such as com-
mand setting are not needed.
For detailed information on external output and alarm functions, refer to the user's manual of
the controller that you use.
<Reference>
Judgment output reading is updated automatically.
Remote output RX (SC-HG1-C → Master)
RX
F
Sensor
Commu-
nication
Function
unit
+20
OUT1
0
+30
OUT2
0
+40
OUT3
0
+50
Alarm
0

4-7 External input

Control of external input from the master unit cable and external input from the SC-HG1-C is by
OR operation.
4-30
E
D
C
B
Slave
Slave
Slave
Slave
unit
unit
unit
unit
14
13
12
11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Example: To check the external output signal and alarm func-
tion signal of slave unit 2, read RX[22], [32], [42], [52].
Example: To check the external output signal and alarm function
signal of the master unit, read RX[20], [30], [40], [50].
A
9
8
7
Slave
Slave
Slave
Slave
unit
unit
unit
unit
10
9
8
7
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Settings from the SC-HG1-C and input from
external input are by OR operation.
When either turns ON, the controller executes
ON operation.
6
5
4
3
Slave
Slave
Slave
Slave
unit
unit
unit
unit
6
5
4
3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
WUME-SCHG1C-4
2
1
0
Slave
Slave
Master
unit
unit
unit
2
1
0
0
0
0
0
0
0
0
0
0
0
0

Advertisement

Table of Contents
loading

Table of Contents