Setting The Alarm Log - Siemens SINUMERIK 840D sl Commissioning Manual

Base software and hmi sl
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

Restart the HMI sl
Restart HMI sl. This data is only converted during startup.
14.3.3

Setting the alarm log

Procedure
HMI sl (IM9)
Commissioning Manual, 01/2008, 6FC5397-1DP10-3BA0
1.
Select the "Diagnosis" operating area.
2.
Press the "Alarm log" and "Settings" softkeys.
3.
Enter a number in the "Number of entries" field to change the
maximum number of administered raised and cleared events.
You can specify a value between 0 and 32000.
4.
In field "Write mode file", select
• "off" if the changes are not to be written to a file;
• "on every event" if every change is to be written to a file;
• "time controlled" if the file is to be overwritten after a particular
period of time. An additional input field called "Time interval"
appears in which you can specify a time in seconds.
Configuring alarms
14.3 Configuring an alarm log
133

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinumerik 840de sl

Table of Contents