7.4 USB interface

7.4
USB interface
Maximum USB cable length 5 m
7.5

PROFINET/Ethernet connection

Maximum length of the PROFINET/Ethernet cable 100 m (90 m BASIC- Link plus 2 x 5 m
CHANNEL- Link)
7.6

SITOP UPS1100 connections

Connections 1.2 Ah/2.5 Ah/3.2 Ah/5 Ah
Connection X1
The connections "X1+" and "X1-" are used to transfer power between the SITOP UPS1600
and the SITOP UPS1100.
1. Ensure that the cables are dimensioned corresponding to the fuses in the
SITOP UPS1100 and the impedances between SITOP UPS1600 and SITOP UPS1100
are the same.
2. Only connect charged batteries with one another.
Connection X2
Connections "X2-1" and "X2-2" serve to transfer data between SITOP UPS1600 and
SITOP UPS1100 (see Image 7-1 Wiring (Page 150)).
When several battery modules are used, note the following:
● Up to 6 battery modules of the same type can be connected together in parallel.
● If different battery modules are connected in parallel, relay 2 flashes (battery defective).
No calculations with regard to charge and remaining buffer time are performed. The
battery modules are not charged, but buffering is possible.
● If more than six battery modules are connected in parallel, relay 2 flashes (battery
defective). No calculations with regard to charge and remaining buffer time are
performed. Charging and buffering, however, is possible.