Maintenance And Testing; Specifications; Regulatory Information - Carrier Kilsen KAL740 Installation Sheet

Addressable supervised siren / relay module
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Module configuration
The module is configured using the DIP switch 8:
If DIP switch 8 is ON the module operates as a supervised
relay module.
If DIP switch 8 is OFF the module operates as a sounder
module.
The relay output provides only the voltage received from the
auxiliary power supply (24 VDC) – ensure that this is sufficient
for your installation.
The module will only allow sounders to be silenced from the
control panel if configured to operate as a sounder module (the
default setting).
Output connections
A maximum of 8 solenoid bells may be connected to the
supervised line. A 15 kΩ end-of-line resistor must be installed
at the end of the supervised line.
Addressing
Each module requires a numeric address between 128 and
252 for identification purposes. This is set using DIP switches
1-7. See the address table at the end of this document.
Status LED
The status LED is lit constantly during alarm.

Maintenance and testing

Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
To test the module:
1.
Configure the module as an output to be activated by a
detector or manual call point.
2.
Remove a detector head from its base or activate a
manual call point.
3.
If the status LED and control panel fail to indicate the test
all connections should be checked and the module
address verified.

Specifications

Operating voltage
Loop current consumption
at 24 VDC (standby)
at 35 VDC (standby)
Alarm
Current consumption
24 VDC aux. supply (standby)*
24 VDC aux. supply (alarm)*
End-of-line resistor
Relay contact rating
Max.switching voltage
Nominal current
Operating temperature
Storage temperature
2 / 16
22 to 38 VDC
110 µA
135 µA
<3.6 mA
6 mA
9 mA
15 kΩ
AC: 42 V peak / DC: 30 V
AC: 0.5 A / DC: 1 A
−10 to +50ºC
−10 to +70ºC
Relative humidity
Weight
Dimensions
* Excluding loop devices

Regulatory information

This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Certification
Certification body
0370
Declaration of
360-4109-0999
Performance number
Year of first CE marking
08
Product identification
KAL740
Intended use
See the product Declaration of Performance
Declared performance
See the product Declaration of Performance
Manufacturer
Carrier Manufacturing Poland Spòlka Z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland.
Authorized EU manufacturing
representative: Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
2012/19/EU (WEEE directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste in
the European Union. For proper recycling,
return this product to your local supplier
upon the purchase of equivalent new
equipment, or dispose of it at designated
collection points. For more information see:
recyclethis.info.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND
INSTALLATION BY QUALIFIED PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY "AUTHORIZED DEALER" OR
"AUTHORIZED RESELLER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers
and product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/ or scan the QR code:
10 to 95% (non condensing)
370 g
180 × 142 × 77 mm
P/N 10-5151-501-105-02 • ISS 09JUN21