Table 9-3
Comments
Burst pulses on power supply ca‐
bles
Burst pulses on data and signal ca‐
bles
Electrostatic discharge (ESD)
Electrostatic air discharge (ESD)
Surge on power supply cables
Electromagnetic RF fields
Induced conducted interference
Not applicable for shielded cables and symmetric ports
1)
An external fuse must be provided to comply with the requirement (e.g. Lightning conductor
2)
BVTAD24, Dehn & Söhne company)
Ambient conditions
The module can be used under the following conditions:
(Also observe the operating conditions of the ET 200SP system)
Table 9-4
Operation
Storage/transport
Table 9-5
Comments
Operating temperature
Storage and transport temperature
Relative humidity
Contaminant concentration
Analog input module AI 2xSG 4-/6-wire HS (7MH4134-6LB00-0DA0)
Manual, 09/2018, A5E41867508A-AB
Requirements: Interference immunity in industrial area in accordance with EN 61000-6-2
Standard
DIN EN 61000-4-2 :2009
DIN EN 61000-4-3 :2011
DIN EN 61000-4-4 :2013
DIN EN 61000-4-5 :2015
DIN EN 61000-4-6 :2014
IEC 61000-4-2 :2008
IEC 61000-4-3 :2006
+A1:2007
2)
+A2:2010
IEC 61000-4-4 :2012
IEC 61000-4-5 :2014
IEC 61000-4-6 :2014
NAMUR NE21:2011
DIN EN 61131-2 :2008
IEC 61131-2 :2007
Operating conditions in accordance with IEC 60721
Climatic requirements
Vertical installation
Horizontal installa‐
tion
9.2 Electrical, EMC and climatic requirements
Severity level
±2.0 kV 5/50 ns/5 kHz
±2.0 kV 5/50 ns/100 kHz
±2.0 kV 5/50 ns/5 kHz
±2.0 kV 5/50 ns/100 kHz
2, 4, 6 kV direct/indirect
2, 4, 6, 8 kV
±1.0 kV line to line
±2.0 kV line to earth
80 MHz to 3 GHz: 20 V/m
10 kHz to 80 MHz: 10 V
IEC60721-3-3:
Class 3K3, stationary use, weather-proofed
IEC 60721-3-2
class 2K4 without precipitation
Ambient conditions
Areas of application
-25 to +50 °C
-25 to +60 °C
-40 to +70 °C
5 ... 95%
No condensation; corre‐
sponds to relative humidity
(RH) stress level 2 to
DIN IEC 61131-2
SO
: < 0.5 ppm
RH < 60%, no condensation
2
H
S: < 0.1 ppm
2
Technical specifications
eff
51