Siemens SIMATIC ET 200SP Manual page 48

Analog input module ai 2xsg 4-/6-wire hs
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Technical specifications
Power loss
Power loss, typical
Address area
Address area per module, max.
● Standard
● Oversampling
Analog inputs
Number of analog inputs
Cycle time (all channels), min.
Analog input with oversampling
● Values per cycle, max.
● Resolution, min.
Input ranges (rated values), voltages
● Input resistance
● ± 0.5 ... +320 mV/V
Cable length shielded, max.
Connection
Sensor voltage monitoring
Value refers to use of a 7MH4702-8AG cable with a minimum voltage of 3 V DC at the sensor)
1)
Generation of analog input values
Measuring principle
Integration and conversion time / resolution per
channel
● Resolution with overrange (bits including sign),
max.
Measured value filter
Notch filter
● Conversion time per channel
46
1.2 W; without sensor supply
16 bytes inputs, 8 bytes outputs
32 bytes inputs, 8 bytes outputs
2; differential inputs
100 μs
14
100 μs
Signal cable: Typical 45*10
sensor cable: Typical 3*10
16 bits including sign (oversampling)
28 bits including sign (normal/isochronous mode)
≤ 500 m
4-wire or 6-wire technology
Typical ≤ 0.5 V
Delta-sigma
● 28 bit (normal/isochronous mode)
● 16 bits (oversampling)
● Line filter (50/60 Hz; typical 80 dB)
● Average value filter 0.01 .. 655.35 ms
● Low-pass filter 0.1 .. 6553.5 Hz
● Filter order 1 .. 4
0.1 .. 1000.0 Hz
Quality 5.00 ... 250.00
100 μs
Analog input module AI 2xSG 4-/6-wire HS (7MH4134-6LB00-0DA0)
Ω
6
Ω
6
Manual, 09/2018, A5E41867508A-AB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7mh4134-6lb00-0da0

Table of Contents