Technical specifications
9.2 Electrical, EMC and climatic requirements
Table 9-2
Comments
Emission of radio interference
(interference field strength)
Emission on power supply cables Class A: Industrial environment:
Emission conducted Ethernet
Note
Radio interference is possible
This is a device of class A. The device may cause radio interference in residential areas.
Implement appropriate measures (e.g.: use in 8MC cabinets) to prevent radio interference.
50
Requirements: Interference emission in industrial area in accordance with EN 61000‑6‑4
Standard
Class A industrial environment:
IEC/CISPR 16-2-3 :2006
EN55016-2-3 :2006
IEC/CISPR 16-2-1 :2009
EN 55016-2-1 :2004
EN 61000-6-4: 2007+A1:2011
IEC/CISPR 22 :2008
EN55022 :2010
Analog input module AI 2xSG 4-/6-wire HS (7MH4134-6LB00-0DA0)
Limits
30 – 230 MHz, 40 dB(mV/m) Q
230 – 1000 MHz, 47 dB(mV/m)
Q
--
1 GHz to 3 GHz / 76 dB(mV/m)
peak, 56 dB(mV/m) average
3 GHz to 6 GHz / 80 dB(mV/m)
Class A: Industrial environment
0.15 ... 0.5 MHz, 79 dB (μV) Q
0.15 ... 0.5 MHz, 66 dB (μV) M
0.5 ... 30 MHz, 73 dB (μV) Q
0.5 ... 30 MHz, 60 dB (μV) M
0.15 ... 0.5 MHz:
53 dB (μA) to 43 dB (μA) Q
40 dB (μA) – 30 dB (μA) M
0.5 ... 30 MHz:
43 dB (μA) to 30 dB (μA) M