Mode 3-1(single source) (Default MBP wiring mode)
1. Input:
connect mian-ground cable (PE) to chassis first;
short 'AC input terminal N/N' with 'busbar #1', then connect AC cable(N);
short 'AC input terminal mL1/bL1/bL2/bL3' with 'busbar #4', then connect AC
cable(L1);
connect 'AC input terminal mL2/mL3' to AC cable(L2/L3).
2. Output:
connect ground cable (PE) to chassis first;
short '
AC segment
short '
AC segment
3. Connect to UPS:
Remove all the busbar of the UPS, then connect the UPS to MBP with '
MBP accessory
UPS1' in
terminal N/N' with 'buabar #1', then connect AC cable(N);
terminal L1/L2/L3' with 'busbar #3', then connect AC cable(L).
.