Dangerous voltage levels are present within the system. It should be opened
exclusively by qualified service personnel.
High leakage current, earth connection essential before connecting supply.
Precautions must be taken for all handling, Wear rubber gloves and boots.
d
The MBP connection instructions and operation described in the manual
must be followed in the indicated order.
The upstream circuit breaker for Normal AC/Bypass AC must be easily
accessible. The unit can be disconnected from AC power source by opening
this circuit breaker.
An additional AC contactor is used for backfeed protection and must comply
with IEC/EN 62040-1 (the creep age and clearance distances shall meet the
basic insulation requirements for pollution degree 2).
Disconnection and overcurrent protection devices shall be provided by
others for permanently connected AC input (Normal AC/Bypass AC) and AC
output circuits.
Check that the indications on the rating plate correspond to your AC
powered system and to the actual electrical consumption of all the
equipment to be connected to the system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the
equipment and shall be easily accessible
Never install the system near liquids or in an excessively damp
environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry
place.
The admissible storage temperature range is -25°C to +60°C.
The unit is heavy: wear safety shoes and use vacuum lifter preferentially for
handling operations.
All handling operations will require at least two people (unpacking, lifting,
installation in rack system).
46