Configuring The Electric Actuator; Setting Up Modbus Communication; Protocol - Samson TROVIS 5724-8 Series Mounting And Operating Instructions

Electric actuator with process controller without failsafe action and with fail-safe action for heating and cooling applications
Hide thumbs Also See for TROVIS 5724-8 Series:
Table of Contents

Advertisement

5.5 Configuring the electric ac-
tuator
Ready-configured systems are available to
facilitate configuration. As a result, the user
only needs to change very few settings to
adapt the device to the application. The user
selects the system code number and changes
configuration items in the TROVIS-VIEW soft-
ware. All the configuration items and pa-
rameters are listed in section 10.2.
Tip
All ready-configured applications as well as
all configuration items and parameters are
described in detail in the associated configu-
ration manual u KH 5724-8. This configura-
tion manual can be downloaded from the
SAMSON website (u www.samsongroup.
com) and is available in the [?] menu in the
TROVIS-VIEW software.
Î Perform the application-specific configu-
ration in TROVIS-VIEW. See documenta-
tion on TROVIS-VIEW software
u EB 6661.
Î Establish connection between the electric
actuator and TROVIS-VIEW software:
− Firmware version 1.1x: over Blue-
tooth, see Table 3 and u EB 6661
for configuration. The electric actua-
tor with process controller must be
added to the Windows
− Firmware version 2.1x: over Modbus
(see section 5.6)
Î We recommend writing down the config-
uration made in section 10.5.
EB 5724-8 EN
5.6 Setting up Modbus commu-
The firmware version 2.1x of the electric
actuator with process controller is fitted with
an RS-485 interface to connect it to a
communication network. The RS-485 data
transfer uses an SSP or Modbus RTU

protocol.

Î See section 10.3 for supported Modbus
Fit the first and last bus participant of the RS-
485 bus with an external bus termination.
The electric actuator with process controller
can be connected to a control station over
Modbus and can be configured using TRO-
VIS-VIEW. Various communications protocol
(SSP or Modbus RTU slave) and a bus con-
necting cable are used for various functions.
See section 3.5.
We recommend the setting P r = A P. With
this setting the electric actuator with process
controller automatically detects the required
protocol. See section 5.6.1.
5.6.1
device list.
®
The RS-485 data transfer is performed auto-
matically using an SSP or Modbus RTU pro-
tocol.
− Setting -1: none
Mounting and start-up
nication
functions.
Note
Tip
Protocol
27

Advertisement

Table of Contents
loading